Schneider Electric LC1D65AFE7 IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 115VAC 50/60Hz coil, open
Schneider Electric
$386.40
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 115 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Protective Cover:
- with
- Utilisation Category:
- AC-4 || AC-1 || AC-3 || AC-3e
- Height:
- 122 mm
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- [Icw] Rated Short-Time Withstand Current:
- 640 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
- Sustainable Offer Status:
- Green Premium product
- [Uc] Control Circuit Voltage:
- 115 V AC 50/60 Hz
- Range:
- TeSys || TeSys Deca
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Device Short Name:
- LC1D
- Mounting Support:
- plate || rail
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Signaling Circuit Frequency:
- 25...400 Hz
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Fire Resistance:
- 850°C IEC 60695-2-1
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Electrical Durability:
- 1.4 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V || 1.45 Mcycles 65 A AC-3e <= 440 V
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Depth:
- 120 mm
- Product Certifications:
- CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
- Protective Treatment:
- THIEC 60068-2-30
- Pole Contact Composition:
- 3 NO
- Rohs Exemption Information:
- Yes
- Eu Rohs Directive:
- Compliant
- Overvoltage Category:
- III
- Power Dissipation Per Pole:
- 9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
- Range Of Product:
- TeSys Deca
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Tightening Torque:
- control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
- Mercury Free:
- Yes
- Control Circuit Type:
- AC 50/60 Hz standard
- Environmental Disclosure:
- ENVPEP1503009EN
- Hold-In Power Consumption In Va:
- 13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
- Country of Origin:
- France
- Operating Time:
- 4...19 ms opening || 12...26 ms closing
- Net Weight:
- 0.86 kg
- Warranty:
- 18 months
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Contactor Application:
- motor control || resistive load
- Heat Dissipation:
- 4-5 W at 50/60 Hz
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
- Maximum Horse Power Rating:
- 40 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 5 hp at 115 V AC 50/60 Hz for 1 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 20 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 20 hp at 230/240 V AC 50/60 Hz for 3 phase
- Minimum Switching Current:
- 5 mA for Signaling circuit