Schneider Electric LC1D80F7 IEC contactor, TeSys Deca, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VAC 50/60Hz coil, open
Schneider Electric
$363.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 150A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 175A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947
- Inrush Power In Va:
- 245-245 VA 60 Hz cos phi 0.75 (at 20°C) || 245-245 VA 50 Hz cos phi 0.75 (at 20°C)
- Rohs Exemption Information:
- Yes
- Pvc Free:
- Yes
- Mechanical Durability:
- 4 Mcycles
- Operating Time:
- 20...35 ms closing || 6...20 ms opening
- Device Short Name:
- LC1D
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Mounting Support:
- rail || plate
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Height:
- 127 mm
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Poles Description:
- 3P
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1100 A at 440 V for power circuit conforming to IEC 60947
- Protective Treatment:
- THIEC 60068-2-30
- Range Of Product:
- TeSys Deca
- Motor Power Kw:
- 22 kW at 220...230 V AC 50/60 Hz (AC-3) || 37 kW at 380...400 V AC 50/60 Hz (AC-3) || 45 kW at 415...440 V AC 50/60 Hz (AC-3) || 55 kW at 500 V AC 50/60 Hz (AC-3) || 45 kW at 660...690 V AC 50/60 Hz (AC-3) || 15 kW at 400 V AC 50/60 Hz (AC-4) || 22 k
- Range:
- TeSys
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 125 A (at 60°C) for power circuit
- Control Circuit Type:
- AC 50/60 Hz standard
- Rated Breaking Capacity:
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Product Or Component Type:
- contactor
- [Ie] Rated Operational Current:
- 125 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC-3e for power circuit
- Average Impedance:
- 0.8 mOhm - Ith 125 A 50 Hz for power circuit
- Contactor Application:
- motor control || resistive load
- Product Certifications:
- CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
- Sustainable Offer Status:
- Green Premium product
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)
- Fire Resistance:
- 850°C IEC 60695-2-1
- Control Circuit Voltage Limits:
- 0.85...1.1 Uc -40-55°C operational AC 60 Hz || 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-55°C operational AC 50 Hz || 1...1.1 Uc 55-70°C operational AC 50/60 Hz
- Overvoltage Category:
- III
- Pole Contact Composition:
- 3 NO
- [Icw] Rated Short-Time Withstand Current:
- 640 A 40°C - 10 s for power circuit || 990 A 40°C - 1 s for power circuit || 135 A 40°C - 10 min for power circuit || 320 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
- Depth:
- 130 mm
- Weight:
- 1.59 kg
- Climatic Withstand:
- IACS E10 exposure to damp heat
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Maximum Horse Power Rating:
- 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors || 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 30 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 60 hp at 460/480 V AC 50/60 Hz for 3 phas
- Utilisation Category:
- AC-3 || AC-3e || AC-4 || AC-1
- Coil Technology:
- without built-in suppressor module
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - ca
- Signaling Circuit Frequency:
- 25...400 Hz
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Power Dissipation Per Pole:
- 5.1 W AC-3 || 12.5 W AC-1 || 5.1 W AC-3e
- Pollution Degree:
- 3
- Tightening Torque:
- control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.