- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
- Warranty:
- 18 months
- Average Impedance:
- 1.6 mOhm - Ith 60 A 50 Hz for power circuit
- Fire Resistance:
- 850°C IEC 60695-2-1
- Power Dissipation Per Pole:
- 5.8 W AC-1
- Environmental Disclosure:
- ENVPEP1503009EN
- Depth:
- 120 mm
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Overvoltage Category:
- III
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Signaling Circuit Frequency:
- 25...400 Hz
- Control Circuit Voltage Limits:
- 0.1...0.3 Uc -40-70°C drop-out DC || 0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- [Ie] Rated Operational Current:
- 60 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Protective Cover:
- with
- Flame Retardance:
- V1 conforming to UL 94
- Device Short Name:
- LC1D
- Electrical Durability:
- 0.7 Mcycles 60 A AC-1 <= 440 V
- Eu Rohs Directive:
- Compliant
- Range Of Product:
- TeSys Deca
- Protective Treatment:
- THIEC 60068-2-30
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Poles Description:
- 4P
- Net Weight:
- 1.165 kg
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Country of Origin:
- France
- Toxic Heavy Metal Free:
- Yes
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Utilisation Category:
- AC-1
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Rated Breaking Capacity:
- 800 A at 440 V for power circuit conforming to IEC 60947
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
- Control Circuit Type:
- DC standard
- Pole Contact Composition:
- 4 NO
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
- Product Or Component Type:
- contactor
- Tightening Torque:
- control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
- Operating Time:
- 50±15 % ms closing || 16...24 ms opening
- Reach Free Of Svhc:
- Yes
- Pollution Degree:
- 3
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Sustainable Offer Status:
- Green Premium product