Schneider Electric

Schneider Electric LC1F1400 contactor body withou coil, TeSys F, 3P(3NO), AC-1, <=1000V AC 1400A, with coil LX1/ LX9, 110…500V AC 40/400Hz, LX4, 110...440V DC

(No reviews yet) Write a Review
SKU:
LC1F1400
MPN:
LC1F1400
Condition:
New
Mounting Support:
plate
Country of Origin:
Czechia
Product Or Component Type:
contactor
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open6 Gn for 1/2 sine wave (11 ms) || shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
[Icw] Rated Short-Time Withstand Current:
8000 A 40°C - 10 s || 6000 A 40°C - 30 s || 4500 A 40°C - 1 min || 4000 A 40°C - 3 min || 2600 A 40°C - 10 min
[Uc] Control Circuit Voltage:
100...500 V AC 40...400 Hz with LX1/LX9 coil || 110...440 V DC with LX4 coil
Irms Rated Making Capacity:
2100 A AC conforming to IEC 60947-4-1
Contactor Application:
resistive load
Operating Altitude:
9842.52 ft (3000 m) without derating
Utilisation Category:
AC-1
Environmental Disclosure:
ENVPEP110206EN
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Mercury Free:
Yes
Pole Contact Composition:
3 NO
Average Impedance:
0.1 mOhm - Ith 1400 A 50 Hz
Connections - Terminals:
power circuit bar 2 || power circuit bolted connection || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible with cable end || control circuit screw clamp terminals
Poles Description:
3P
Heat Dissipation:
18-18 W
[Ie] Rated Operational Current:
1400 A 40°C) <= 440 V AC AC-1
Rohs Exemption Information:
Yes
Associated Fuse Rating:
1600 A gG at <= 440 V conforming to IEC 60947-4-1
Product Name:
TeSys F
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Certifications:
CSA || EAC || CB Scheme || CCC || UL || UKCA
Warranty:
18 months
Rated Breaking Capacity:
2100 A conforming to IEC 60947-4-1
Tightening Torque:
power circuit 58 N.m || control circuit 1.2 N.m
Ambient Air Temperature For Operation:
-5-40°C
Permissible Ambient Air Temperature Around The Device:
-40-60°C
Inrush Power In Va:
1600-2400 VA, 40...400 Hz cos phi 0.9 (at 20°C)with LX1/LX9 coil || 2000-2200 VA (at 20°C)with LX4 coil
Power Dissipation Per Pole:
150 W AC-1
Mechanical Durability:
0.5 Mcycles
Net Weight:
29 kg
Ambient Air Temperature For Storage:
-60-80°C
Weight:
29 kg
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Standards:
EN 60947-4-1 || IEC 60947-1 || JIS C8201-4-1 || IEC 60947-4-1 || EN 60947-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Operating Time:
40...50 ms closing with LX1/LX9 coil || 100...170 ms opening with LX1/LX9 coil || 50...60 ms closing with LX4 coil || 40...50 ms opening with LX4 coil
Maximum Operating Rate:
600 cyc/h 55°C
Overvoltage Category:
III
[Ith] Conventional Free Air Thermal Current:
1400 A (at 40°C)
Device Short Name:
LC1F
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Sustainable Offer Status:
Green Premium product
Control Circuit Voltage Limits:
operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil || drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil || operational: 0.85...1.1 Uc DC with LX4 coil || drop-out: 0.2...0.35 Uc DC with LX4 coil
Circularity Profile:
ENVEOLI1102006EN
$8,030.00