Schneider Electric

Schneider Electric LC1G2254EHEA Contactor, high power, TeSys Giga, advanced version, AC-1, <= 440V, 330A, 4 pole/NO, 48-130VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G2254EHEA
MPN:
LC1G2254EHEA
Condition:
New
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Inrush Power In Va:
260-260 VA
Utilisation Category:
AC-3 || AC-3e || AC-1 || AC-5a || AC-5b || AC-6a || AC-6b || DC-1 || DC-3 || DC-5
Average Impedance:
0.00015 Ohm
Operating Time:
40...70 ms closing || 15...50 ms opening
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Auxiliary Contact Composition:
1 NO + 1 NC
Eu Rohs Directive:
Compliant with Exemptions
Hold-In Power Consumption In W:
5.0-5.0 W
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Pole Contact Composition:
4 NO
Environmental Disclosure:
ENVPEP2105013
Connection Pitch:
35 mm
Contactor Application:
power switching
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Circularity Profile:
ENVEOLI2105013
Tightening Torque:
18 N.m
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Protective Treatment:
TH
[Ith] Conventional Free Air Thermal Current:
330 A (at 40°C)
Sustainable Offer Status:
Green Premium product
Overvoltage Category:
III
Device Short Name:
LC1G
China Rohs Regulation:
X
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Associated Fuse Rating:
250 A aM at <= 440 V for motor || 200 A aM at <= 690 V for motor || 400 A gG at <= 690 V
Color:
dark grey
Mercury Free:
Yes
Range Of Product:
TeSys Giga
Poles Description:
4P
Maximum Horse Power Rating:
60 hp at 200/208 V 60 Hz || 75 hp at 230/240 V 60 Hz || 150 hp at 460/480 V 60 Hz || 150 hp at 575/600 V 60 Hz
Halogen Content Performance:
Halogen free plastic parts product
Rated Breaking Capacity:
2050 A at 440 V
Depth:
193 mm
Net Weight:
5.1 kg
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1
Inrush Power In W:
190 W
Ambient Air Temperature For Operation:
-25-60°C
Coil Technology:
built-in bidirectional peak limiting
[Ie] Rated Operational Current:
225 A (at <60°C) at <= 440 V AC-3 || 330 A (at <40°C) at <= 1000 V AC-1
Pvc Free:
Yes
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || UL 60335-1 || UL 60335-2-40:Annex JJ
[Uc] Control Circuit Voltage:
48...130 V AC 50/60 Hz || 48...130 V DC
Range:
TeSys
Irms Rated Making Capacity:
2720 A at 440 V
$1,730.00

Description

TeSys Giga high power contactor, 4 poles (4 NO) for category AC-1 applications up to 330A @440V. It provides a 48-130V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 143mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose