Schneider Electric

Schneider Electric LC1K0601N7 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 6A, 1 NC aux., 400 to 415VAC coil

(No reviews yet) Write a Review
SKU:
LC1K0601N7
MPN:
LC1K0601N7
Condition:
New
Ambient Air Temperature For Storage:
-50-80°C
Mounting Support:
plate || rail
[Ui] Rated Insulation Voltage:
power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
Sustainable Packaging:
Yes
Height:
58 mm
[Ith] Conventional Free Air Thermal Current:
20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
Contactor Application:
motor control
Maximum Operating Rate:
3600 cyc/h
Signaling Circuit Frequency:
<= 400 Hz
Overvoltage Category:
III
Inrush Power In Va:
30-30 VA (at 20°C)
[Uc] Control Circuit Voltage:
400...415 V AC 50/60 Hz
Control Circuit Voltage Limits:
operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Rated Breaking Capacity:
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
Hold-In Power Consumption In Va:
4.5-4.5 VA (at 20°C)
Circularity Profile:
ENVEOLI1503003EN
Control Circuit Type:
AC 50/60 Hz
Ip Degree Of Protection:
IP2X VDE 0106
Poles Description:
3P
Eu Rohs Directive:
Compliant
Tightening Torque:
0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
Sustainable Offer Status:
Green Premium product
Depth:
57 mm
Average Impedance:
3 mOhm - Ith 20 A 50 Hz for power circuit
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
Minimum Switching Current:
5 mA for Signaling circuit
[Icw] Rated Short-Time Withstand Current:
90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
Toxic Heavy Metal Free:
Yes
Heat Dissipation:
1.3-1.3 W
Operating Altitude:
6561.68 ft (2000 m) without derating
Standards:
EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Non Overlap Distance:
0.5 mm
Range:
TeSys
Insulation Resistance:
> 10 MOhm for Signaling circuit
Pole Contact Composition:
3 NO
[Ie] Rated Operational Current:
6 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 6 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Auxiliary Contact Composition:
1 NC
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Warranty:
18 months
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Product Certifications:
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Motor Power Kw:
1.5 kW 220...230 V AC 50/60 Hz AC-3 || 2.2 kW 380...415 V AC 50/60 Hz AC-3 || 3 kW 440/690 V AC 50/60 Hz AC-3 || 1.5 kW 220...230 V AC 50/60 Hz AC-3e || 2.2 kW 380...415 V AC 50/60 Hz AC-3e || 3 kW 440/690 V AC 50/60 Hz AC-3e || 1.5 kW 220...230 V AC
Minimum Switching Voltage:
17 V for Signaling circuit
$57.00