Schneider Electric

Schneider Electric LC1K0901T7 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 9A, 1 NC aux., 480VAC coil

(No reviews yet) Write a Review
SKU:
LC1K0901T7
MPN:
LC1K0901T7
Condition:
New
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
Minimum Switching Current:
5 mA for Signaling circuit
Contactor Application:
motor control || resistive load
Warranty:
18 months
Sustainable Offer Status:
Green Premium product
Standards:
EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Operating Time:
10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
Reach Free Of Svhc:
Yes
Width:
45 mm
Product Certifications:
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Auxiliary Contact Composition:
1 NC
Insulation Resistance:
> 10 MOhm for Signaling circuit
Minimum Switching Voltage:
17 V for Signaling circuit
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Poles Description:
3P
Rated Breaking Capacity:
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
Depth:
57 mm
Mercury Free:
Yes
Toxic Heavy Metal Free:
Yes
Product Or Component Type:
contactor
Circularity Profile:
ENVEOLI1503003EN
Hold-In Power Consumption In Va:
4.5-4.5 VA (at 20°C)
Pole Contact Composition:
3 NO
[Icw] Rated Short-Time Withstand Current:
90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Mechanical Durability:
10 Mcycles
Heat Dissipation:
1.3-1.3 W
Utilisation Category:
AC-3 || AC-3e || AC-1 || AC-4
Signaling Circuit Frequency:
<= 400 Hz
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Inrush Power In Va:
30-30 VA (at 20°C)
Electrical Durability:
1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
[Ith] Conventional Free Air Thermal Current:
20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
Rohs Exemption Information:
Yes
Connections - Terminals:
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
Country of Origin:
France
Range:
TeSys
Mechanical Robustness:
shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Operating Altitude:
6561.68 ft (2000 m) without derating
Sustainable Packaging:
Yes
Overvoltage Category:
III
Device Application:
control
Eu Rohs Directive:
Compliant
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Auxiliary Contacts Type:
instantaneous 1 NC
$75.00