Schneider Electric LC1K0901U7 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 9A, 1 NC aux., 230 to 240VAC coil
Schneider Electric
$75.00
LC1K0901U7 is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 240V 50/60Hz AC coil and 1NC auxiliary contact. LC1K0901U7 is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 4kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it includes a 240V 50/60Hz AC coil and 1NC built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Provides a control circuit compatible with 50Hz and 60Hz supplies and 1NC built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
- Mercury Free:
- Yes
- Rohs Exemption Information:
- Yes
- Environmental Disclosure:
- ENVPEP1503003EN
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
- Motor Power Kw:
- 2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440/690 V AC 50/60 Hz AC-3 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440/690 V AC 50/60 Hz AC-3e || 2.2 kW 220...230 V AC 50/
- Overvoltage Category:
- III
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- Depth:
- 57 mm
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Warranty:
- 18 months
- Eu Rohs Directive:
- Compliant
- Mechanical Durability:
- 10 Mcycles
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Range:
- TeSys
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Sustainable Offer Status:
- Green Premium product
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Utilisation Category:
- AC-3 || AC-3e || AC-1 || AC-4
- Sustainable Packaging:
- Yes
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Circularity Profile:
- ENVEOLI1503003EN
- Heat Dissipation:
- 1.3-1.3 W
- Mechanical Robustness:
- shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Signaling Circuit Frequency:
- <= 400 Hz
- Country of Origin:
- France
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Electrical Durability:
- 1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
- Contactor Application:
- motor control || resistive load
- Poles Description:
- 3P
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Auxiliary Contact Composition:
- 1 NC
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
- Toxic Heavy Metal Free:
- Yes
- Control Circuit Type:
- AC 50/60 Hz
- Reach Free Of Svhc:
- Yes