- Product Or Component Type:
- reversing contactor
- Utilisation Category:
- AC-3 || AC-1 || AC-3e
- Protective Treatment:
- TH IEC 60068-2-30
- Warranty:
- 18 months
- Pollution Degree:
- 3
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Motor Power Kw:
- 30 kW at 220...230 V AC 50-60 Hz || 55 kW at 380...400 V AC 50-60 Hz || 59 kW at 415 V AC 50-60 Hz || 59 kW at 440 V AC 50-60 Hz || 75 kW at 500 V AC 50-60 Hz || 80 kW at 660...690 V AC 50-60 Hz || 65 kW at 1000 V AC 50-60 Hz
- Device Short Name:
- LC2D
- [Icw] Rated Short-Time Withstand Current:
- 250 A 40°C - 10 min for power circuit || 550 A 40°C - 1 min for power circuit || 950 A 40°C - 10 s for power circuit || 1100 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
- Operating Time:
- 20...50 ms closing || 6...20 ms opening
- Signaling Circuit Frequency:
- 25...400 Hz
- Protective Cover:
- with
- Circularity Profile:
- ENVEOLI100405EN
- Mounting Support:
- plate || rail
- Depth:
- 148 mm
- Climatic Withstand:
- IACS E10
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Product Certifications:
- BV || CCC || CSA || DNV || GL || RINA || UL || EAC || UKCA
- Interlocking Type:
- electrical || mechanical
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Power Dissipation Per Pole:
- 24 W AC-1 || 7.9 W AC-3 || 7.9 W AC-3e
- Hold-In Power Consumption In Va:
- 2-18 VA 20°C) 0.3 60 Hz || 2-18 VA 20°C) 0.3 50 Hz
- Ambient Air Temperature For Storage:
- -60-80°C
- Inrush Power In Va:
- 280-350 VA 60 Hz 0.8 20°C) || 280-350 VA 50 Hz 0.8 20°C)
- Overvoltage Category:
- III
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Maximum Operating Rate:
- 2400 cyc/h 60°C
- [Ie] Rated Operational Current:
- 200 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 115 A (at <60°C) at <= 440 V AC AC-3 for power circuit
- [Ith] Conventional Free Air Thermal Current:
- 200 A (at 60°C) for power circuit
- Mercury Free:
- Yes
- Tightening Torque:
- control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
- Country of Origin:
- Czechia
- Device Presentation:
- preassembled with reversing power busbar
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Range:
- TeSys
- Control Circuit Type:
- AC 50/60 Hz
- Electrical Durability:
- 0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1260 A at 440 V for power circuit conforming to IEC 60947
- Rohs Exemption Information:
- Yes
- Heat Dissipation:
- 3-8 W 50/60 Hz
- Maximum Horse Power Rating:
- 30 hp at 200/208 V AC 60 Hz for 3 phase motors || 40 hp at 230/240 V AC 60 Hz for 3 phase motors || 75 hp at 460/480 V AC 60 Hz for 3 phase motors || 100 hp at 575/600 V AC 60 Hz for 3 phase motors
- Flame Retardance:
- V1 conforming to UL 94
- Weight:
- 6.35 kg