- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- [Uc] Control Circuit Voltage:
- 220 V AC 50/60 Hz
- Protective Cover:
- with
- Electrical Durability:
- 2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 12 A AC-3e <= 440 V
- Mounting Support:
- plate || rail
- Product Certifications:
- DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
- Device Short Name:
- LC2D
- Pvc Free:
- Yes
- Protective Treatment:
- TH IEC 60068-2-30
- Poles Description:
- 3P
- Overvoltage Category:
- III
- Maximum Horse Power Rating:
- 1 hp at 115 V AC 60 Hz for 1 phase motors || 2 hp at 230/240 V AC 60 Hz for 1 phase motors || 3 hp at 200/208 V AC 60 Hz for 3 phase motors || 3 hp at 230/240 V AC 60 Hz for 3 phase motors || 7.5 hp at 460/480 V AC 60 Hz for 3 phase motors || 10 hp a
- Sustainable Offer Status:
- Green Premium product
- Mechanical Durability:
- 15 Mcycles
- Depth:
- 86 mm
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Power Dissipation Per Pole:
- 1.56 W AC-1 || 0.36 W AC-3 || 0.36 W AC-3e
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- [Icw] Rated Short-Time Withstand Current:
- 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- [Ie] Rated Operational Current:
- 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Mercury Free:
- Yes
- Range:
- TeSys || TeSys Deca
- Toxic Heavy Metal Free:
- Yes
- Connections - Terminals:
- power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp
- Device Presentation:
- preassembled with reversing power busbar
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Pole Contact Composition:
- 3 NO
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Rohs Exemption Information:
- Yes
- Heat Dissipation:
- 2-3 W 50/60 Hz
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Pollution Degree:
- 3
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Width:
- 90 mm
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Warranty:
- 18 months
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Product Name:
- TeSys Deca
- Environmental Disclosure:
- ENVPEP1501004
- Irms Rated Making Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1