- Control Circuit Voltage Limits:
- 0.1...0.3 Uc -40-70°C drop-out DC || 0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
- Electrical Durability:
- 1.5 Mcycles 40 A AC-3 <= 440 V || 0.7 Mcycles 60 A AC-1 <= 440 V || 1.5 Mcycles 40 A AC-3e <= 440 V
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Net Weight:
- 2.02 kg
- Motor Power Kw:
- 11 kW at 220...230 V AC 50-60 Hz || 18.5 kW at 380...400 V AC 50-60 Hz || 22 kW at 415 V AC 50-60 Hz || 22 kW at 440 V AC 50-60 Hz || 22 kW at 500 V AC 50-60 Hz || 30 kW at 660...690 V AC 50-60 Hz
- Ambient Air Temperature For Storage:
- -60-80°C
- Reach Free Of Svhc:
- Yes
- Inrush Power In W:
- 19-19 W 20°C)
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Pollution Degree:
- 3
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
- Flame Retardance:
- V1 conforming to UL 94
- [Ie] Rated Operational Current:
- 40 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 60 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Pvc Free:
- Yes
- Hold-In Power Consumption In W:
- 7.4-7.4 W 20°C
- Product Certifications:
- UL || CSA || RINA || GOST || CCC || DNV || LROS (Lloyds register of shipping) || GL || BV || UKCA
- Protective Treatment:
- TH IEC 60068-2-30
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- [Uc] Control Circuit Voltage:
- 24 V DC
- Overvoltage Category:
- III
- Mechanical Durability:
- 10 Mcycles
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Environmental Disclosure:
- ENVPEP1503009EN
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Device Presentation:
- preassembled with reversing power busbar
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Control Circuit Type:
- DC standard
- Rohs Exemption Information:
- Yes
- Product Name:
- TeSys Deca
- Eu Rohs Directive:
- Compliant
- Maximum Horse Power Rating:
- 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 30 hp at 575/600 V AC 60 Hz for 3 phase motors || 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 3 hp at 115 V AC 60 Hz for 1 phase motors || 30 hp
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Country of Origin:
- France
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Device Short Name:
- LC2D
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Protective Cover:
- with
- Product Or Component Type:
- reversing contactor
- Power Dissipation Per Pole:
- 2.4 W AC-3 || 5.4 W AC-1 || 2.4 W AC-3e
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Average Impedance:
- 1.5 mOhm - Ith 60 A 50 Hz for power circuit
- Mounting Support:
- plate || rail
- Weight:
- 2.02 kg