- Contactor Application:
- motor control || resistive load
- Flame Retardance:
- V1 conforming to UL 94
- Interlocking Type:
- mechanical
- Pole Contact Composition:
- 3 NO
- Electrical Durability:
- 1 Mcycles 66 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3e
- Product Certifications:
- CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
- Pollution Degree:
- 3
- Environmental Disclosure:
- ENVPEP1607010EN
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
- Height:
- 122 mm
- Overvoltage Category:
- III
- Hold-In Power Consumption In Va:
- 1-1 VA 20°C) 50/60 Hz
- Control Circuit Type:
- AC 50/60 Hz AC/DC electronic || DC AC/DC electronic
- Eu Rohs Directive:
- Compliant with Exemptions
- Maximum Horse Power Rating:
- 5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp
- Heat Dissipation:
- 0.7-0.7 W 50/60 Hz
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Product Name:
- Tesys Deca green || TeSys Deca
- Device Short Name:
- LC2D
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Circularity Profile:
- ENVEOLI1607010EN
- Width:
- 119 mm
- Sustainable Offer Status:
- Green Premium product
- Rated Breaking Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Control Circuit Voltage Limits:
- <= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC || 0.8...1.1 Uc -40-60°C operational DC || 1...1.1 Uc 60-70°C operational AC/DC
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Connections - Terminals:
- control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible with cable end || power circuit Ev
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC-1 for power circuit || 66 A (at <60°C) at <= 440 V AC-3 for power circuit || 66 A (at <60°C) AC-3e for power circuit
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Depth:
- 120 mm
- Warranty:
- 18 months
- Mounting Support:
- rail || plate
- Color:
- Gray SE GREY 6) || Green SE GREEN 2)
- Power Dissipation Per Pole:
- 9.6 W AC-1 || 6.5 W AC-3 || 6.5 W AC-3e
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Hold-In Power Consumption In W:
- 0.7-0.7 W 20°C
- Coil Technology:
- built-in bidirectional peak limiting
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Weight:
- 2.174 kg
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
- Rohs Exemption Information:
- Yes
- Halogen Content Performance:
- Halogen free plastic parts & cables product
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Operating Time:
- 55...65 ms closing || 20...80 ms opening
- Utilisation Category:
- AC-1 || AC-3 || AC-3e