- Depth:
- 120 mm
- Halogen Content Performance:
- Halogen free plastic parts & cables product
- Rohs Exemption Information:
- Yes
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Interlocking Type:
- mechanical
- Product Certifications:
- CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
- Hold-In Power Consumption In W:
- 0.9-0.9 W 20°C
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Flame Retardance:
- V1 conforming to UL 94
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
- Contactor Application:
- motor control || resistive load
- Circularity Profile:
- ENVEOLI1607010EN
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
- Device Presentation:
- preassembled with reversing power busbar
- [Ue] Rated Operational Voltage:
- power circuit 690 V AC 25...400 Hz
- Control Circuit Voltage Limits:
- <= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC/DC || 1...1.1 Uc 60-70°C operational AC/DC
- Environmental Disclosure:
- ENVPEP1607010EN
- Electrical Durability:
- 1 Mcycles 66 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3e
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Control Circuit Type:
- AC 50/60 Hz AC/DC electronic || DC AC/DC electronic
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Fire Resistance:
- 850°C IEC 60695-2-1
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Inrush Power In Va:
- 23-23 VA 50/60 Hz 20°C)
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC-1 for power circuit || 66 A (at <60°C) at <= 440 V AC-3 for power circuit || 66 A (at <60°C) AC-3e for power circuit
- Range:
- TeSys || TeSys Deca
- Signaling Circuit Frequency:
- 25...400 Hz
- Net Weight:
- 2.174 kg
- Weight:
- 2.174 kg
- Device Short Name:
- LC2D
- Heat Dissipation:
- 0.9-0.9 W 50/60 Hz
- Mechanical Durability:
- 6 Mcycles
- Coil Technology:
- built-in bidirectional peak limiting
- Pollution Degree:
- 3
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Mounting Support:
- plate || rail
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- [Uc] Control Circuit Voltage:
- 48...130 V AC 50/60 Hz || 48...130 V DC
- Inrush Power In W:
- 19-19 W 20°C
- Ambient Air Temperature For Storage:
- -60-80°C