Schneider Electric

Schneider Electric LC2DT40BD TeSys Deca changeover contactor - 4P(4 NO) - AC-1 - <= 440 V 40 A - 24 V DC coil

(No reviews yet) Write a Review
SKU:
LC2DT40BD
MPN:
LC2DT40BD
Condition:
New
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Protective Cover:
with
Minimum Switching Voltage:
17 V for Signaling circuit
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mounting Support:
plate || rail
Overvoltage Category:
III
Rated Breaking Capacity:
450 A at 440 V for power circuit conforming to IEC 60947
Power Dissipation Per Pole:
3.2 W AC-1
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Product Certifications:
UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
Pvc Free:
Yes
Environmental Disclosure:
ENVPEP110230EN
[Icw] Rated Short-Time Withstand Current:
50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Electrical Durability:
1.4 Mcycles 40 A AC-1 <= 440 V
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m connector flat Ø 6 mm || power circuit 1.7 N.m connector Philips No 2 || power circuit 1.7 N.m screw cl
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Ip Degree Of Protection:
IP20 front face IEC 60529
Net Weight:
0.85 kg
Fire Resistance:
850°C IEC 60695-2-1
Operating Time:
53.55...72.45 ms closing || 16...24 ms opening
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Control Circuit Type:
DC standard
Time Constant:
28 ms
Pollution Degree:
3
Interlocking Type:
mechanical
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Device Presentation:
preassembled with reversing power busbar
[Ie] Rated Operational Current:
40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Circularity Profile:
ENVEOLI1102030EN
Auxiliary Contact Composition:
1 NO + 1 NC
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Protective Treatment:
TH IEC 60068-2-30
Insulation Resistance:
> 10 MOhm for Signaling circuit
Product Name:
TeSys Deca
Operating Altitude:
0...9842.52 ft (0...3000 m)
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
Inrush Power In W:
5.4-5.4 W 20°C
Rohs Exemption Information:
Yes
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current:
5 mA for Signaling circuit
Mercury Free:
Yes
$523.00

Description

TeSys D changeover contactor, 4 poles (4NO), for non-inductive load applications up to 40A/690V AC-1. It provides 24V DC coils, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired changeover power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
View AllClose