Schneider Electric LDA36600U33X Circuit breaker, PowerPacT L, 600A, 3 pole, 600VAC, 14kA, I-Line, Micrologic 3.3S, 80%, ABC
Schneider Electric
$7,968.00
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 600A, 3 pole, circuit breaker has an interrupting rating of 14kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3S trip unit and an LSI function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Mounting Mode:
- I-Line bracket)
- Eu Rohs Directive:
- Compliant with Exemptions
- Pollution Degree:
- 3 IEC 60947-1
- Utilisation Category:
- category A
- Environmental Disclosure:
- ENVPEP2206029EN
- Network Frequency:
- 50/60 Hz
- Color:
- Black
- Device Application:
- distribution
- Length:
- 31 mm
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Ambient Air Temperature For Storage:
- -50-85°C
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Communication Interface:
- Modbus || Ethernet
- Wire Stripping Length:
- 31 mm
- Product Or Component Type:
- circuit breaker
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Pvc Free:
- Yes
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Product Name:
- PowerPact L
- Sustainable Offer Status:
- Green Premium product
- Mounting Height:
- 6 in
- Product Certifications:
- UL || CSA || NOM
- Suitability For Isolation:
- yes IEC 60947-2
- Breaking Capacity Code:
- D
- Height:
- 340 mm
- Range:
- PowerPact
- Depth:
- 110 mm
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Net Weight:
- 6.2 kg
- Electrical Connection:
- I-Line connection, line || lugs, load
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3 S, LSI
- Rohs Exemption Information:
- Yes
- Warranty:
- 18 months
- Tightening Torque:
- 50-50 N.m 70-240 mm² (2 x AWG 2/0...500 kcmil)
- Terminal Identifier:
- AL600LF52K3
- Circuit Breaker Application:
- HACR rated
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Circularity Profile:
- ENVEOLI2206029EN
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Support:
- bracket
- Height:
- 6 in
- Ip Degree Of Protection:
- front cover IP40
- Poles Description:
- 3P
- Local Signaling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Continuous Current Rating:
- 0.8
- Line Rated Current:
- 600-600 A