- Rohs Exemption Information:
- Yes
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Product Certifications:
- UL || CSA || NOM
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- Poles Description:
- 3P
- Device Short Name:
- L-Frame
- Product Name:
- PowerPact L
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Ambient Air Temperature For Operation:
- -2-70 °C
- Ambient Air Temperature For Storage:
- -50-85 °C
- Net Weight:
- 6.2 kg
- Height:
- 340 mm
- Product Or Component Type:
- circuit breaker
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Breaking Capacity Code:
- D
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mercury Free:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Color:
- Black
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Control Type:
- toggle
- Terminal Identifier:
- AL600LS52K3
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Network Frequency:
- 50/60 Hz
- Trip Unit Name:
- MicroLogic 3.3
- Width:
- 140 mm
- Depth:
- 110 mm
- Tightening Torque:
- 50-50 N.m 70-240 mm² (2 x AWG 2/0...500 kcmil)
- Line Rated Current:
- 600-600 A
- Suitability For Isolation:
- yes IEC 60947-2
- Mounting Support:
- lug
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Environmental Disclosure:
- ENVPEP1406010EN
- Eu Rohs Directive:
- Compliant
- Utilisation Category:
- category A
- Range:
- PowerPact
- Ip Degree Of Protection:
- front cover IP40
- Circuit Breaker Application:
- HACR rated
- Circularity Profile:
- ENVEOLI1406010EN
- Communication Interface:
- Modbus || Ethernet
- Mounting Mode:
- unit mount lug)
- Pollution Degree:
- 3 IEC 60947-1
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Continuous Current Rating:
- 0.8
- Pvc Free:
- Yes
- Electrical Connection:
- terminal nut, line || lugs, load
- Wire Stripping Length:
- 31 mm || 61 mm
- Device Application:
- distribution
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- QN-QUOTE-REQUEST:
- true