Schneider Electric LGA36400U33X Molded Case Circuit Breaker 600V 400A
Schneider Electric
$5,969.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3S trip unit and an LSI function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Electrical Connection:
- I-Line connection, line || lugs, load
- Mounting Support:
- bracket
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Utilisation Category:
- category A
- Continuous Current Rating:
- 0.8
- Line Rated Current:
- 400-400 A
- Product Certifications:
- UL || CSA || NOM
- Color:
- Black
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Eu Rohs Directive:
- Compliant with Exemptions
- Suitability For Isolation:
- yes IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ip Degree Of Protection:
- front cover IP40
- Range:
- PowerPact
- Ambient Air Temperature For Operation:
- -2-70 °C
- Device Application:
- distribution
- Mounting Mode:
- I-Line bracket)
- Circuit Breaker Application:
- HACR rated
- Wire Stripping Length:
- 31 mm
- Height:
- 340 mm
- Circularity Profile:
- ENVEOLI2206029EN
- Mounting Height:
- 6 in
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3 S, LSI
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206029EN
- Trip Unit Name:
- MicroLogic 3.3 S
- Tightening Torque:
- 50-50 N.m 95-240 mm² (AWG 3/0...500 kcmil)
- Warranty:
- 18 months
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Protection Technology:
- current limiter
- Pvc Free:
- Yes
- Rohs Exemption Information:
- Yes
- Poles Description:
- 3P
- Control Type:
- toggle
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Awg Gauge:
- AWG 3/0...500 kcmil aluminium/copper
- Device Short Name:
- L-Frame
- Mercury Free:
- Yes
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Breaking Capacity Code:
- G
- Net Weight:
- 6.2 kg
- Phase Connection:
- ABC
- Product Or Component Type:
- circuit breaker
- Pollution Degree:
- 3 IEC 60947-1
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ambient Air Temperature For Storage:
- -50-85 °C
- Communication Interface:
- Modbus || Ethernet
- Network Frequency:
- 50/60 Hz
- Product Name:
- PowerPact L
- Width:
- 140 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Sustainable Offer Status:
- Green Premium product
- Depth:
- 110 mm
- Terminal Identifier:
- AL600LF52K3
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View