- Continuous Current Rating:
- 1
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ambient Air Temperature For Storage:
- -50-85 °C
- Product Certifications:
- UL || CSA || NOM
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Trip Unit Name:
- MicroLogic 5.3 A
- Line Rated Current:
- 400-400 A
- Mounting Support:
- lug
- Warranty:
- 18 months
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Control Type:
- toggle
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Rohs Exemption Information:
- Yes
- Mercury Free:
- Yes
- Circuit Breaker Application:
- HACR rated
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 5.3 A, LSI
- Circularity Profile:
- ENVEOLI2206029EN
- Product Or Component Type:
- circuit breaker
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Terminal Identifier:
- AL600LS52K3
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Network Frequency:
- 50/60 Hz
- Sustainable Offer Status:
- Green Premium product
- Color:
- Black
- Device Short Name:
- L-Frame
- Communication Interface:
- Modbus || Ethernet
- Device Application:
- distribution
- Poles Description:
- 3P
- Depth:
- 110 mm
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Name:
- PowerPact L
- Utilisation Category:
- category A
- Net Weight:
- 6.2 kg
- Ip Degree Of Protection:
- front cover IP40
- Ambient Air Temperature For Operation:
- -2-70 °C
- Suitability For Isolation:
- yes IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Width:
- 140 mm
- Eu Rohs Directive:
- Compliant with Exemptions
- Breaking Capacity Code:
- G
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Height:
- 340 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Wire Stripping Length:
- 31 mm || 61 mm
- Range:
- PowerPact
- Pvc Free:
- Yes
- Pollution Degree:
- 3 IEC 60947-1
- Mounting Mode:
- unit mount lug)
- Electrical Connection:
- lugs, line || lugs, load
- Environmental Disclosure:
- ENVPEP2206029EN
- QN-QUOTE-REQUEST:
- true