Schneider Electric LGL46250U31X Molded Case Circuit Breaker 600V 400A

(No reviews yet) Write a Review
SKU:
LGL46250U31X
UPC:
785901308614
Condition:
New
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Device Short Name:
L-Frame
Control Type:
toggle
Eu Rohs Directive:
Compliant with Exemptions
Network Frequency:
50/60 Hz
Color:
Black
Product Certifications:
UL || CSA || NOM
Poles Description:
4P
Mounting Support:
lug
Mercury Free:
Yes
Utilisation Category:
category A
Environmental Disclosure:
ENVPEP2206029EN
Line Rated Current:
250-250 A
Electrical Connection:
lugs, line || lugs, load
Rohs Exemption Information:
Yes
Height:
340 mm
Sustainable Offer Status:
Green Premium product
Pollution Degree:
3 IEC 60947-1
Local Signalling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Ambient Air Temperature For Operation:
-2-70 °C
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ambient Air Temperature For Storage:
-50-85 °C
Mounting Mode:
unit mount lug)
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Ip Degree Of Protection:
front cover IP40
Trip Unit Name:
MicroLogic 3.3
Width:
140 mm
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Continuous Current Rating:
0.8
Trip Unit Technology:
electronic, standard, MicroLogic 3.3, LI
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Product Name:
PowerPact L
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Product Or Component Type:
circuit breaker
Suitability For Isolation:
yes IEC 60947-2
Tightening Torque:
50-50 N.m 35-300 mm² (AWG 2...600 kcmil) || 50-50 N.m 35-240 mm² (AWG 2...500 kcmil)
Depth:
110 mm
Communication Interface:
Modbus || Ethernet
Warranty:
18 months
Pvc Free:
Yes
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Net Weight:
6.2 kg
Wire Stripping Length:
31 mm
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Device Application:
distribution
Circularity Profile:
ENVEOLI2206029EN
Breaking Capacity Code:
G
Terminal Identifier:
AL400L61K4
Range:
PowerPact
Awg Gauge:
AWG 2...600 kcmil copper || AWG 2...500 kcmil aluminium
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Brochure:
View
Catalog:
View
Datasheet:
View
$5,581.00

Description

PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 250A, 4 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3 trip unit and an LI function. This unit has lugs on both the line and load sides. This circuit breaker has a continuous current rating of 80%. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose