- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mounting Mode:
- unit mount lug)
- Circularity Profile:
- ENVEOLI2206029EN
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Utilisation Category:
- category A
- Ambient Air Temperature For Operation:
- -2-70 °C
- Wire Stripping Length:
- 31 mm || 61 mm
- Rohs Exemption Information:
- Yes
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Electrical Connection:
- lugs, line || lugs, load
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Mercury Free:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Width:
- 140 mm
- Breaking Capacity Code:
- J
- Suitability For Isolation:
- yes IEC 60947-2
- Line Rated Current:
- 400-400 A
- Environmental Disclosure:
- ENVPEP2206029EN
- Ip Degree Of Protection:
- front cover IP40
- Eu Rohs Directive:
- Compliant with Exemptions
- Color:
- Black
- Circuit Breaker Application:
- HACR rated
- Net Weight:
- 6.2 kg
- Sustainable Offer Status:
- Green Premium product
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Support:
- lug
- Range:
- PowerPact
- Poles Description:
- 3P
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Control Type:
- toggle
- Continuous Current Rating:
- 0.8
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Trip Unit Name:
- MicroLogic 5.3 A
- Depth:
- 110 mm
- Height:
- 340 mm
- Device Application:
- distribution
- Network Frequency:
- 50/60 Hz
- Product Name:
- PowerPact L
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Device Short Name:
- L-Frame
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Communication Interface:
- Modbus || Ethernet
- Warranty:
- 18 months
- Pvc Free:
- Yes
- Pollution Degree:
- 3 IEC 60947-1
- Product Certifications:
- UL || CSA || NOM
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Terminal Identifier:
- AL600LS52K3
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 5.3 A, LSI
- QN-QUOTE-REQUEST: