Schneider Electric LJL36600M38X Molded Case Circuit Breaker 600V 600A

(No reviews yet) Write a Review
SKU:
LJL36600M38X
UPC:
785901853602
Condition:
New
Local Signalling:
ready 1 LED green) || alarm 1 LED 95 % Ith red) || switched off (OFF) 1 trip indicator green)
Terminal Identifier:
AL600LS52K3
Device Short Name:
L-Frame
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Pvc Free:
Yes
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Ambient Air Temperature For Storage:
-50-85 °C
Line Rated Current:
600-600 A
Eu Rohs Directive:
Compliant with Exemptions
Depth:
110 mm
Height:
340 mm
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mercury Free:
Yes
Rohs Exemption Information:
Yes
Breaking Capacity Code:
J
Width:
140 mm
Device Application:
distribution
Network Frequency:
50/60 Hz
Sustainable Offer Status:
Green Premium product
Color:
Black
Mounting Support:
lug
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Suitability For Isolation:
yes IEC 60947-2
Circularity Profile:
ENVEOLI2206029EN
Ip Degree Of Protection:
front cover IP40
Wire Stripping Length:
31 mm || 61 mm
Communication Interface:
Modbus || Ethernet
Control Type:
toggle
Utilisation Category:
category A
Net Weight:
6.2 kg
Electrical Connection:
lugs, line || lugs, load
Trip Unit Name:
MicroLogic 2.3 M
Poles Description:
3P
Warranty:
18 months
Product Certifications:
UL || CSA || NOM
Pollution Degree:
3 IEC 60947-1
Environmental Disclosure:
ENVPEP2206029EN
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Trip Unit Technology:
electronic, standard, MicroLogic 2.3 M, LSoI
Awg Gauge:
2 x AWG 2/0...500 kcmil aluminium/copper
[Ith] Conventional Free Air Thermal Current:
312-520 A
Mounting Mode:
unit mount lug)
Circuit Breaker Application:
HACR rated
Tightening Torque:
50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Range:
PowerPact
Product Or Component Type:
Motor Circuit Protector
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Product Name:
PowerPact L
Ambient Air Temperature For Operation:
-2-70 °C
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Breaking Capacity:
100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
Brochure:
View
Catalog:
View
Datasheet:
View
$8,604.00

Description

PowerPacT L-Frame motor circuit protectors (MCP) are instantaneous-trip circuit breakers designed to offer short circuit protection for motors. PowerPacT L-Frame motor circuit protectors are available with electronic trip units. The unique design of the PowerPacT MCPs accommodates transient motor inrush current without nuisance tripping. These motor protectors accept the same accessories and terminals as the equivalent PowerPacT L circuit breaker. PowerPacT L protectors are available in 3 pole unit mount, I-Line, and plug in constructions. This PowerPacT L, 600A, 3 pole, MCP has an interrupting rating of 25kA at 600VAC. This protector provides MicroLogic with a 2.3M trip unit. This unit has lugs on both the line and load sides. This motor circuit protector has a continuous current rating of 80%. PowerPacT L motor circuit protectors comply to UL, CSA, and IEC standards.