Schneider Electric LJP36400U33X Molded Case Circuit Breaker 600V 250A

(No reviews yet) Write a Review
SKU:
LJP36400U33X
UPC:
3.60649E+12
Condition:
New
Width:
140 mm
Continuous Current Rating:
0.8
Rohs Exemption Information:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Local Signalling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Wire Stripping Length:
31 mm || 61 mm
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Trip Unit Technology:
electronic, standard, MicroLogic 3.3 S, LSI
Circuit Breaker Application:
HACR rated
Circularity Profile:
ENVEOLI2206029EN
Poles Description:
3P
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Device Short Name:
L-Frame
Eu Rohs Directive:
Compliant with Exemptions
Ambient Air Temperature For Operation:
-2-70 °C
Range:
PowerPact
Utilisation Category:
category A
Ambient Air Temperature For Storage:
-50-85 °C
Product Certifications:
UL || CSA || NOM
Trip Unit Name:
MicroLogic 3.3 S
Warranty:
18 months
Product Name:
PowerPact L
Net Weight:
6.2 kg
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Environmental Disclosure:
ENVPEP2206029EN
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Line Rated Current:
400-400 A
Breaking Capacity:
100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
Tightening Torque:
50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil) || 50-50 N.m 35-300 mm² (AWG 2...600 kcmil)
Network Frequency:
50/60 Hz
Pollution Degree:
3 IEC 60947-1
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Electrical Connection:
terminal nut, line || lugs, load
Protection Technology:
current limiter
Height:
340 mm
Mercury Free:
Yes
Communication Interface:
Modbus || Ethernet
Sustainable Offer Status:
Green Premium product
Suitability For Isolation:
yes IEC 60947-2
Device Application:
distribution
Mounting Support:
lug
Product Or Component Type:
circuit breaker
Depth:
110 mm
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Color:
Black
Awg Gauge:
2 x AWG 2/0...500 kcmil aluminium/copper
Terminal Identifier:
AL600LS52K3
Pvc Free:
Yes
Mounting Mode:
unit mount lug)
Control Type:
toggle
Breaking Capacity Code:
J
Ip Degree Of Protection:
front cover IP40
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric LJP36400U33X Molded Case Circuit Breaker 600V 250A
  • Schneider Electric LJP36400U33X Molded Case Circuit Breaker 600V 250A
$9,071.00

Description

PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3S trip unit and an LSI function. This unit has terminal nuts on the line side and lugs on the load side. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose