- Width:
- 140 mm
- Rohs Exemption Information:
- Yes
- Height:
- 340 mm
- Circuit Breaker Application:
- HACR rated
- Trip Unit Name:
- MicroLogic 3.3 S
- Product Name:
- PowerPact L
- Ip Degree Of Protection:
- front cover IP40
- Circularity Profile:
- ENVEOLI2206029EN
- Line Rated Current:
- 600-600 A
- Product Or Component Type:
- circuit breaker
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3 S, LSI
- Suitability For Isolation:
- yes IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mounting Mode:
- unit mount lug)
- Net Weight:
- 6.2 kg
- Network Frequency:
- 50/60 Hz
- Continuous Current Rating:
- 0.8
- Device Application:
- distribution
- Utilisation Category:
- category A
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Sustainable Offer Status:
- Green Premium product
- Mounting Support:
- lug
- Ambient Air Temperature For Storage:
- -50-85 °C
- Breaking Capacity Code:
- J
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Eu Rohs Directive:
- Compliant with Exemptions
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Wire Stripping Length:
- 31 mm || 61 mm
- Depth:
- 110 mm
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Terminal Identifier:
- AL600LS52K3
- Range:
- PowerPact
- Ambient Air Temperature For Operation:
- -2-70 °C
- Device Short Name:
- L-Frame
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Poles Description:
- 3P
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Pvc Free:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Electrical Connection:
- terminal nut, line || lugs, load
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Communication Interface:
- Modbus || Ethernet
- Environmental Disclosure:
- ENVPEP2206029EN
- Product Certifications:
- UL || CSA || NOM
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mercury Free:
- Yes
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Color:
- Black
- Control Type:
- toggle
- Pollution Degree:
- 3 IEC 60947-1
- Warranty:
- 18 months
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In