Schneider Electric

Schneider Electric LUCA05FU Std Control 1.25-5A 110-240V

(No reviews yet) Write a Review
SKU:
LUCA05FU
UPC:
3389110364026
Condition:
New
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Typical Current Consumption:
280 mA 110...240 V AC I maximum while closing with LUB12 || 280 mA 110...240 V AC I maximum while closing with LUB32 || 280 mA 110...240 V AC I maximum while closing with LUB38 || 280 mA 110...220 V DC I maximum while closing with LUB12 || 280 mA 110
Standards:
EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier
Net Weight:
0.135 kg
Resistance To Electrostatic Discharge:
8 kV 3 in open air IEC 61000-4-2 || 8 kV 4 on contact IEC 61000-4-2
Utilisation Category:
AC-44 || AC-41 || AC-43
Halogen Content Performance:
Halogen free plastic parts product
Height:
66 mm
Ip Degree Of Protection:
IP20 front panel and wired terminals IEC 60947-1 || IP20 other faces IEC 60947-1 || IP40 front panel outside connection zone IEC 60947-1
Ambient Air Temperature For Operation:
-25-70 °C
Operating Time:
35 ms opening with LUB12 control circuit || 35 ms opening with LUB32 control circuit || 35 ms opening with LUB38 control circuit || 50 ms closing with LUB12 control circuit || 50 ms closing with LUB32 control circuit || 50 ms closing with LUB38 contr
Range:
TeSys
Eu Rohs Directive:
Compliant with Exemptions
Resistance To Fast Transients:
2 kV 3 serial link IEC 61000-4-4 || 4 kV 4 all circuits except for serial link IEC 61000-4-4
Compatibility Code:
LUCA
Product Name:
TeSys Ultra
Shock Resistance:
10 gn power poles open IEC 60068-2-27 || 15 gn power poles closed IEC 60068-2-27
Circularity Profile:
ENVEOLI100414
Device Application:
motor control || motor protection
Protective Treatment:
TH IEC 60068
Ambient Air Temperature For Storage:
-40-85 °C
Fixing Mode:
plug-in front face)
Control Circuit Voltage Limits:
88...264 V AC 110...240 V in operation || 88...242 V DC 110...220 V in operation || 55 V AC 110...240 V drop-out || 55 V DC 110...220 V drop-out
Product Or Component Type:
standard control unit
Load Type:
3-phase motor self-cooled
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Motor Power Kw:
1.5 kW 400...440 V AC 50/60 Hz || 2.2 kW 500 V AC 50/60 Hz || 3 kW 690 V AC 50/60 Hz
Heat Dissipation:
2-2 W control circuit with LUB12 || 3-3 W control circuit with LUB32 || 3-3 W control circuit with LUB38
Tripping Threshold:
14.2 x Ir +/- 20 %
Function Available:
protection against phase failure and phase imbalance || protection against overload and short-circuit || manual reset || earth fault protection
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947-6-2
Depth:
60 mm
Device Short Name:
LUCA
Mercury Free:
Yes
Network Frequency:
40...60 Hz
Immunity To Voltage Dips:
70 % / 500 ms IEC 61000-4-11
Product Certifications:
CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine
Non-Dissipating Shock Wave:
1 kV serial mode IEC 60947-6-2 || 2 kV common mode IEC 60947-6-2
Pvc Free:
Yes
Phase Failure Sensitivity:
yes
Width:
45 mm
Range Of Product:
TeSys Ultra
Fire Resistance:
960 °C parts supporting live components IEC 60695-2-12 || 650 °C IEC 60695-2-12
Thermal Overload Class:
class 10 40-60 Hz -25-70 °C IEC 60947-6-2 || class 10 40-60 Hz -25-70 °C UL 508
Immunity To Microbreaks:
3 ms
[Ui] Rated Insulation Voltage:
690 V IEC 60947-6-2 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Sustainable Offer Status:
Green Premium product
Immunity To Radioelectric Fields:
10 V IEC 61000-4-6
Rohs Exemption Information:
Yes
Warranty:
18 months
Thermal Protection Adjustment Range:
1.25-5 A
[Ue] Rated Operational Voltage:
690 V AC
Vibration Resistance:
2 gn 5-300 Hz power poles open IEC 60068-2-6 || 4 gn 5-300 Hz power poles closed IEC 60068-2-6
Product Specific Application:
basic protection requirements for motor starters: overload and short-circuit
Environmental Disclosure:
ENVPEP080204EN
Safe Separation Of Circuit:
400 V SELV between the control and auxiliary circuits IEC 60947-1 || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
Product Compatibility:
power base LUB12 || power base LUB32 || power base LUB38 || power base LUB120 || power base LUB320 || power base LUB380 || reversing contactor breaker LU2B12FU || reversing contactor breaker LU2B32FU || reversing contactor breaker LU2B38FU
Resistance To Radiated Fields:
10 V/m 3 IEC 61000-4-3
Operating Altitude:
6561.68 ft (2000 m)
[Uc] Control Circuit Voltage:
110...240 V AC || 110...220 V DC
Catalog:
View
Datasheet:
View
$120.00

Description

TeSys U standard control unit to be inserted in power bases LUB12, LUB32, LUB38 to form a TeSys U starter controller, for 3-phase motor applications up to 1.5kW@400V. It provides full protection to motors with a rated current Ir 1.25-5A (Ir adjustable), overload tripping class 10, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). To be used with a 110-240V AC / 110-220V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).