- Depth:
- 72 mm
- Environmental Disclosure:
- ENVPEP1304004EN
- Rohs Exemption Information:
- Yes
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Local Signalling:
- ON/OFF indication
- Number Of Protected Poles:
- 4
- Sustainable Offer Status:
- Green Premium product
- Wire Stripping Length:
- 14 mm for top or bottom connection
- Overvoltage Category:
- IV
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kVEN/IEC 60947-2
- Utilisation Category:
- category A EN/IEC 60947-2
- Tightening Torque:
- 2-2 N.m top or bottom
- Magnetic Tripping Limit:
- 8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
- Heat Dissipation:
- 10.8-10.8 W 415 V - 6 A
- Halogen Content Performance:
- Halogen free plastic parts & cables product
- Tropicalisation:
- 2 IEC 60068-1
- Product Or Component Type:
- miniature circuit-breaker
- Circularity Profile:
- N/A
- Color:
- Gray
- Poles Description:
- 4P
- Network Frequency:
- 50/60 Hz
- Net Weight:
- 0.48 kg
- Curve Code:
- C
- Contact Position Indicator:
- yes
- Ambient Air Temperature For Operation:
- -30-70 °C
- Pollution Degree:
- 3 EN/IEC 60947-2
- [Ue] Rated Operational Voltage:
- 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 250 V DC
- Earth-Leakage Protection:
- separate block
- Mounting Support:
- DIN rail
- Height:
- 81 mm
- Control Type:
- toggle
- 9 Mm Pitches:
- 8
- Trip Unit Technology:
- thermal-magnetic
- Eu Rohs Directive:
- Compliant with Exemptions
- Mechanical Durability:
- 20000 cycles
- Line Rated Current:
- 6 A 50 °C EN/IEC 60947-2
- Device Application:
- distribution
- Provision For Padlocking:
- padlockable
- Standards:
- EN/IEC 60947-2
- Product Name:
- Multi9 C60
- Mercury Free:
- Yes
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Limitation Class:
- 3
- [Ui] Rated Insulation Voltage:
- 500 V AC 50/60 Hz EN/IEC 60947-2
- Mounting Mode:
- clip-on
- Relative Humidity:
- 95-95 % 55-55 °C
- Device Short Name:
- C60L
- Network Type:
- AC || DC
- Ambient Air Temperature For Storage:
- -40-80 °C
- Connections - Terminals:
- tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
- Breaking Capacity:
- 60 kA Icu <= 250 V DC EN/IEC 60947-2 || 50 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 25 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
- Electrical Durability:
- 10000 cycles
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Range:
- Multi9
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Width:
- 72 mm
- Product Certifications:
- EAC || CCC
- [Ics] Rated Service Breaking Capacity:
- 25 kA 50 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 12.5 kA 50 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 10 kA 50 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 60 kA 100 % EN/IEC 60947-2 - <= 250 V DC
- QN-QUOTE-REQUEST:
- true