Schneider Electric M9F43208 Multi9 C60Bp 2P D 8A 10Ka 480Y/277V Mcb
Schneider Electric
$246.00
This Multi9 C60BP is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 8A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 103mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
- Mercury Free:
- Yes
- Device Application:
- distribution
- Number Of Protected Poles:
- 2
- Line Rated Current:
- 8 A 25 °C EN/IEC 60947-2
- Electrical Durability:
- 10000 cycles
- Eu Rohs Directive:
- Compliant with Exemptions
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Tightening Torque:
- 2.5-2.5 N.m top or bottom
- Device Short Name:
- C60BP
- Width:
- 36 mm
- Pollution Degree:
- 3 EN/IEC 60947-2
- Connections - Terminals:
- tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 8) - rigid || tunnel type terminal top or bottom) 1-16 mm² AWG 18...AWG 8) - flexible with ferrule || tunnel type terminal top or bottom) 1-16 mm² AWG 18...AWG 8) - flexible
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Trip Unit Technology:
- thermal-magnetic
- Earth-Leakage Protection:
- without
- Mounting Mode:
- clip-on
- Operating Altitude:
- 0...6561.68 ft (0...2000 m)
- Product Certifications:
- IEC || CCC || CSA || UL
- Poles Description:
- 2P
- Environmental Disclosure:
- ENVPEP1304004EN
- Circularity Profile:
- N/A
- [Ics] Rated Service Breaking Capacity:
- 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC || 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC || 15 kA 75 % EN/IEC 60947-2 - 240 V AC || 4.5 kA 75 % GB 14048.2 - 440 V AC || 7.5 kA 75 % GB 14048.2 - 415 V AC || 15 kA 75 % GB 14048.2 - 240 V AC
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kVEN/IEC 60947-2
- Halogen Content Performance:
- Halogen free product
- Provision For Padlocking:
- padlockable
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Breaking Capacity:
- 6 kA Icu 440 V AC EN/IEC 60947-2 || 10 kA Icu 415 V AC EN/IEC 60947-2 || 20 kA Icu 240 V AC EN/IEC 60947-2 || 6 kA Icu 440 V AC GB 14048.2 || 10 kA Icu 415 V AC GB 14048.2 || 20 kA Icu 240 V AC GB 14048.2 || 14 kA AIR 240 V AC UL 489 || 10 kA AIR 125
- Wire Stripping Length:
- 14 mm for top or bottom connection
- [Ue] Rated Operational Voltage:
- 240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 440 V AC 50/60 Hz
- Local Signalling:
- ON/OFF indication
- Network Type:
- AC || DC
- Ambient Air Temperature For Operation:
- -30-70 °C
- Color:
- Gray
- Depth:
- 72 mm
- Contact Position Indicator:
- yes
- [Ui] Rated Insulation Voltage:
- 500 V AC EN/IEC 60947-2
- Control Type:
- toggle
- Mounting Support:
- DIN rail
- Mechanical Durability:
- 20000 cycles
- Sustainable Offer Status:
- Green Premium product
- Product Or Component Type:
- miniature circuit-breaker
- Height:
- 103 mm
- Rohs Exemption Information:
- Yes
- Ambient Air Temperature For Storage:
- -40-80 °C
- Tropicalisation:
- 2 IEC 60068-1
- Standards:
- EN/IEC 60947-2 || GB 14048.2 || UL 489 || CSA C22.2 No 5
- Product Name:
- Multi9 C60
- 9 Mm Pitches:
- 4
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Magnetic Tripping Limit:
- 12 x In +/- 20 % AC || 17 x In +/- 20 % DC
- Relative Humidity:
- 95-95 % 55-55 °C
- Curve Code:
- D
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Range:
- Multi9
- Brochure:
- View
- Datasheet:
- View