Schneider Electric M9F52202 Multi9 C60Bpr 2P C 2A 10Ka 480Y/277V Mcb
Schneider Electric
$282.00
This Multi9 C60BPR is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 2A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 127mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
- Trip Unit Technology:
- thermal-magnetic
- Network Type:
- DC || AC
- Circularity Profile:
- N/A
- Relative Humidity:
- 95-95 % 55-55 °C
- Mounting Support:
- DIN rail
- Tropicalisation:
- 2 IEC 60068-1
- Device Short Name:
- C60BPR
- Color:
- Gray
- Depth:
- 72 mm
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Mechanical Durability:
- 20000 cycles
- Range:
- Multi9
- Overvoltage Category:
- IV
- Control Type:
- toggle
- Connections - Terminals:
- ring terminal top or bottom)
- Number Of Protected Poles:
- 2
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Tightening Torque:
- 2-2 N.m top or bottom
- Product Name:
- Multi9 C60
- [Ics] Rated Service Breaking Capacity:
- 4.5 kA 75 % GB 14048.2 - 240 V AC || 7.5 kA 75 % GB 14048.2 || 15 kA 75 % GB 14048.2 || 4.5 kA 75 % EN/IEC 60947-2 - 125 V DC || 7.5 kA 75 % EN/IEC 60947-2 - 440 V AC || 15 kA 75 % EN/IEC 60947-2 - 415 V AC
- Breaking Capacity:
- 6 kA Icu 440 V AC EN/IEC 60947-2 || 10 kA Icu 415 V AC EN/IEC 60947-2 || 20 kA Icu 240 V AC EN/IEC 60947-2 || 6 kA Icu 440 V AC GB 14048.2 || 10 kA Icu 415 V AC GB 14048.2 || 20 kA Icu 240 V AC GB 14048.2 || 14 kA AIR 240 V AC UL 489 || 10 kA AIR 125
- [Ui] Rated Insulation Voltage:
- 500 V AC EN/IEC 60947-2
- Environmental Disclosure:
- ENVPEP1304004EN
- Pollution Degree:
- 3 EN/IEC 60947-2
- Local Signalling:
- ON/OFF indication
- Contact Position Indicator:
- yes
- Product Certifications:
- IEC || CCC || CSA || UL
- Ambient Air Temperature For Storage:
- -40-80 °C
- Rohs Exemption Information:
- Yes
- Halogen Content Performance:
- Halogen free product
- Device Application:
- distribution
- Curve Code:
- C
- Ambient Air Temperature For Operation:
- -30-70 °C
- Eu Rohs Directive:
- Compliant with Exemptions
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Height:
- 127 mm
- Product Or Component Type:
- miniature circuit-breaker
- Mounting Mode:
- clip-on
- Mercury Free:
- Yes
- Electrical Durability:
- 10000 cycles
- Poles Description:
- 2P
- Line Rated Current:
- 2 A 25 °C EN/IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ue] Rated Operational Voltage:
- 240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 440 V AC 50/60 Hz
- 9 Mm Pitches:
- 4
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kVEN/IEC 60947-2
- Standards:
- EN/IEC 60947-2 || GB 14048.2 || UL 489 || CSA C22.2 No 5
- Sustainable Offer Status:
- Green Premium product
- Operating Altitude:
- 0...6561.68 ft (0...2000 m)
- Magnetic Tripping Limit:
- 8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
- Earth-Leakage Protection:
- without
- Width:
- 36 mm
- Provision For Padlocking:
- padlockable
- Brochure:
- View
- Datasheet:
- View