This Multi9 C60BPR is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 10A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 127mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Curve Code:
- D
- Electrical Durability:
- 10000 cycles
- Height:
- 127 mm
- Mechanical Durability:
- 20000 cycles
- Color:
- Gray
- Rohs Exemption Information:
- Yes
- [Ics] Rated Service Breaking Capacity:
- 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC || 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC || 15 kA 75 % EN/IEC 60947-2 - 240 V AC || 4.5 kA 75 % GB 14048.2 - 440 V AC || 7.5 kA 75 % GB 14048.2 - 415 V AC || 15 kA 75 % GB 14048.2 - 240 V AC
- Pollution Degree:
- 3 EN/IEC 60947-2
- Local Signalling:
- ON/OFF indication
- Network Type:
- AC
- Device Short Name:
- C60BPR
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Connections - Terminals:
- ring terminal top or bottom)
- Device Application:
- distribution
- Mounting Mode:
- clip-on
- Ambient Air Temperature For Storage:
- -40-80 °C
- Ambient Air Temperature For Operation:
- -30-70 °C
- Poles Description:
- 3P
- Trip Unit Technology:
- thermal-magnetic
- Halogen Content Performance:
- Halogen free product
- Depth:
- 72 mm
- Product Or Component Type:
- miniature circuit-breaker
- Control Type:
- toggle
- Contact Position Indicator:
- yes
- Tightening Torque:
- 2-2 N.m top or bottom
- Operating Altitude:
- 0...6561.68 ft (0...2000 m)
- Eu Rohs Directive:
- Compliant with Exemptions
- Circularity Profile:
- N/A
- Earth-Leakage Protection:
- without
- Provision For Padlocking:
- padlockable
- Width:
- 54 mm
- [Ui] Rated Insulation Voltage:
- 500 V AC EN/IEC 60947-2
- Mounting Support:
- DIN rail
- Tropicalisation:
- 2 IEC 60068-1
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Product Name:
- Multi9 C60
- Relative Humidity:
- 95-95 % 55-55 °C
- Number Of Protected Poles:
- 3
- Line Rated Current:
- 10 A 25 °C EN/IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- 9 Mm Pitches:
- 6
- Standards:
- EN/IEC 60947-2 || GB 14048.2 || UL 489 || CSA C22.2 No 5
- Product Certifications:
- IEC || CCC || CSA || UL
- Mercury Free:
- Yes
- Environmental Disclosure:
- ENVPEP1304004EN
- Range:
- Multi9
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kVEN/IEC 60947-2
- [Ue] Rated Operational Voltage:
- 240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 440 V AC 50/60 Hz
- Magnetic Tripping Limit:
- 12 x In +/- 20 % AC
- Breaking Capacity:
- 6 kA Icu 440 V AC EN/IEC 60947-2 || 10 kA Icu 415 V AC EN/IEC 60947-2 || 20 kA Icu 240 V AC EN/IEC 60947-2 || 6 kA Icu 440 V AC GB 14048.2 || 10 kA Icu 415 V AC GB 14048.2 || 20 kA Icu 240 V AC GB 14048.2 || 14 kA AIR 240 V AC UL 489 || 10 kA AIR 480
- Brochure:
- View
- Datasheet:
- View