Schneider Electric M9U21125 Multi9 C60H-Dc 1P C 25A 10Ka 250V-Dc Mcb
Schneider Electric
$273.00
This Multi9 C60H-DC is a low voltage miniature circuit breaker (MCB) dedicated to direct current. It is a 1P circuit breaker with 1 protected pole, 25A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 220VDC conforming to EN/IEC 60947-2 standard and 10kA at 220VDC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 3000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 250VDC. The Ui rated insulation voltage is 500VDC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 81mm x (D) 73mm. The weight is 0.128kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.
- Relative Humidity:
- 95-95 % 55-55 °C
- Utilisation Category:
- category A EN/IEC 60947-2
- [Ui] Rated Insulation Voltage:
- 500 V DC EN/IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70 °C
- Rohs Exemption Information:
- Yes
- Toxic Heavy Metal Free:
- Yes
- Local Signalling:
- ON/OFF indication
- Device Application:
- distribution
- Range:
- Multi9
- Mounting Support:
- DIN rail
- Depth:
- 73 mm
- Color:
- Gray
- Number Of Protected Poles:
- 1
- Tropicalisation:
- 2 IEC 60068-2 || 2 GB 14048.2
- Magnetic Tripping Limit:
- 7...10 x In DC
- Tightening Torque:
- 3.5-3.5 N.m top or bottom
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Or Component Type:
- miniature circuit-breaker
- Product Certifications:
- IEC || CCC || UR
- Mounting Mode:
- clip-on
- Network Type:
- DC
- Line Rated Current:
- 25 A 25 °C EN/IEC 60947-2
- Ambient Air Temperature For Storage:
- -40-85 °C
- Height:
- 81 mm
- Sustainable Offer Status:
- Green Premium product
- Circularity Profile:
- N/A
- Provision For Padlocking:
- padlockable
- Width:
- 18 mm
- [Ue] Rated Operational Voltage:
- 250 V DC || 110 V DC || 220 V DC
- Electrical Durability:
- 3000 cycles 250 V DC L/R = 2 ms || 6000 cycles 250 V DC
- Eu Rohs Directive:
- Compliant
- Connections - Terminals:
- tunnel type terminal top or bottom) 1-35 mm² AWG 18...AWG 2) - rigid stranded || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 4) - flexible || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 4) - flexible with ferrule || tun
- Pollution Degree:
- 3 EN/IEC 60947-2
- 9 Mm Pitches:
- 2
- Net Weight:
- 0.128 kg
- Earth-Leakage Protection:
- without
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Product Name:
- Multi9 C60H-DC
- Mercury Free:
- Yes
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Mechanical Durability:
- 20000 cycles
- Curve Code:
- C
- Device Short Name:
- C60H-DC
- Poles Description:
- 1P
- Wire Stripping Length:
- 14 mm for top or bottom connection
- Contact Position Indicator:
- yes
- Breaking Capacity:
- 10 kA Icu 220 V DC EN/IEC 60947-2 || 6 kA Icu 250 V DC EN/IEC 60947-2 || 20 kA Icu 110 V DC EN/IEC 60947-2 || 5 kA AIR 12...250 V DC UL 1077 || 10 kA Icu 220 V DC GB 14048.2 || 6 kA Icu 250 V DC GB 14048.2 || 20 kA Icu 110 V DC GB 14048.2
- Control Type:
- toggle
- Environmental Disclosure:
- ENVPEP120608EN_V0
- [Ics] Rated Service Breaking Capacity:
- 7.5 kA 75 % EN/IEC 60947-2 - 220 V DC || 4.5 kA 75 % EN/IEC 60947-2 - 250 V DC || 15 kA 75 % EN/IEC 60947-2 - 110 V DC || 7.5 kA 75 % GB 14048.2 - 220 V DC || 4.5 kA 75 % GB 14048.2 - 250 V DC || 15 kA 75 % GB 14048.2 - 110 V DC
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kVEN/IEC 60947-2
- Heat Dissipation:
- 3.1-3.1 W 220 V - 25 A
- Standards:
- EN/IEC 60947-2 || GB 14048.2 || UL 1077
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Trip Unit Technology:
- thermal-magnetic
- Brochure:
- View
- Datasheet:
- View