Schneider Electric

Schneider Electric MGA36800 Molded Case Circuit Breaker 600V 800A

(No reviews yet) Write a Review
SKU:
MGA36800
UPC:
785901496793
Condition:
New
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
[Ics] Rated Service Breaking Capacity:
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
Mounting Support:
bracket
Ambient Air Temperature For Storage:
-50-85 °C
Warranty:
18 months
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Breaking Capacity Code:
G
Poles Description:
3P
Terminal Identifier:
AL800M23K
Mercury Free:
Yes
Suitability For Isolation:
yes IEC 60947-2
Product Or Component Type:
circuit breaker
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
Circuit Breaker Application:
HACR rated
Line Rated Current:
800-800 A
Pvc Free:
Yes
Awg Gauge:
3 x AWG 3/0...3 x 500 kcmil aluminium/copper
Sustainable Offer Status:
Green Premium product
Range:
PowerPact
Device Application:
distribution
Magnetic Tripping Current:
1600-8000 A
Quality Labels:
CE
Local Signalling:
1 trip indicator green)
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Eu Rohs Directive:
Compliant with Exemptions
Environmental Disclosure:
ENVPEP2206030EN
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Network Frequency:
50/60 Hz
Utilisation Category:
category A
Circularity Profile:
ENVEOLI2206030EN
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Breaking Capacity:
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
Product Certifications:
UL || CSA || NOM
Wire Stripping Length:
25 mm
Depth:
8.05 in
Product Name:
PowerPact M
Quantity Per Set:
1
Control Type:
operating handle
Electrical Connection:
I-Line connection, line || lugs, load
Trip Unit Name:
ET 1.0
Long Time Pick-Up Adjustment Range:
300...800 A
Ip Degree Of Protection:
IP40
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Mounting Height:
9 in
Mounting Mode:
I-Line bracket)
Height:
12.86 in
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Width:
8.27 in
Color:
Black
Trip Unit Technology:
electronic, basic, ET 1.0,
Pollution Degree:
3 IEC 60947-1
Ambient Air Temperature For Operation:
-25-70 °C
Rohs Exemption Information:
Yes
Continuous Current Rating:
0.8
Net Weight:
29 lb(US)
Brochure:
View
Catalog:
View
Datasheet:
View
$10,608.00

Description

PowerPacT M-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT M-Frame circuit breakers have either a fixed long time electronic trip unit or an adjustable amperage version. This circuit breaker has an electronic trip unit, ET 1.0. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT M circuit breakers are available in 2 and 3-pole unit mount or I-Line construction. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT M, 800A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT M circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose