- Depth:
- 8.05 in
- Breaking Capacity Code:
- G
- Accessory / Separate Part Type:
- control wire ON and OFF end
- Sustainable Offer Status:
- Green Premium product
- Quantity Per Set:
- 1
- Color:
- Black
- Terminal Identifier:
- AL800M23K
- Trip Unit Name:
- ET 1.0
- Product Certifications:
- UL || CSA || NOM
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Width:
- 8.27 in
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Control Type:
- operating handle
- Ambient Air Temperature For Storage:
- -50-85 °C
- Ip Degree Of Protection:
- IP40
- Network Frequency:
- 50/60 Hz
- Rohs Exemption Information:
- Yes
- Mercury Free:
- Yes
- Mounting Support:
- lug
- Pollution Degree:
- 3 IEC 60947-1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ambient Air Temperature For Operation:
- -25-70 °C
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- Environmental Disclosure:
- ENVPEP2206030EN
- Circularity Profile:
- ENVEOLI2206030EN
- Line Rated Current:
- 600-600 A
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Warranty:
- 18 months
- Circuit Breaker Application:
- HACR rated
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Net Weight:
- 29 lb(US)
- Local Signalling:
- 1 trip indicator green)
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Height:
- 12.86 in
- Poles Description:
- 3P
- Wire Stripping Length:
- 25 mm
- Device Application:
- distribution
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
- Eu Rohs Directive:
- Compliant with Exemptions
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Product Or Component Type:
- circuit breaker
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Quality Labels:
- CE
- Suitability For Isolation:
- yes IEC 60947-2
- Utilisation Category:
- category A
- Range:
- PowerPact
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Magnetic Tripping Current:
- 1200-6000 A
- Pvc Free:
- Yes
- Mounting Mode:
- unit mount lug)
- Continuous Current Rating:
- 0.8
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Electrical Connection:
- lugs, load || lugs, line
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Product Name:
- PowerPact M
- QN-QUOTE-REQUEST:
- true