Schneider Electric MGL36600LW Molded Case Circuit Breaker 600V 600A

(No reviews yet) Write a Review
SKU:
MGL36600LW
UPC:
785901955535
Condition:
New
Depth:
8.05 in
Breaking Capacity Code:
G
Accessory / Separate Part Type:
control wire ON and OFF end
Sustainable Offer Status:
Green Premium product
Quantity Per Set:
1
Color:
Black
Terminal Identifier:
AL800M23K
Trip Unit Name:
ET 1.0
Product Certifications:
UL || CSA || NOM
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Width:
8.27 in
[Ics] Rated Service Breaking Capacity:
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
Awg Gauge:
3 x AWG 3/0...3 x 500 kcmil aluminium/copper
Control Type:
operating handle
Ambient Air Temperature For Storage:
-50-85 °C
Ip Degree Of Protection:
IP40
Network Frequency:
50/60 Hz
Rohs Exemption Information:
Yes
Mercury Free:
Yes
Mounting Support:
lug
Pollution Degree:
3 IEC 60947-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ambient Air Temperature For Operation:
-25-70 °C
Long Time Pick-Up Adjustment Range:
300...800 A
Environmental Disclosure:
ENVPEP2206030EN
Circularity Profile:
ENVEOLI2206030EN
Line Rated Current:
600-600 A
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Warranty:
18 months
Circuit Breaker Application:
HACR rated
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Net Weight:
29 lb(US)
Local Signalling:
1 trip indicator green)
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
Height:
12.86 in
Poles Description:
3P
Wire Stripping Length:
25 mm
Device Application:
distribution
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
Eu Rohs Directive:
Compliant with Exemptions
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Product Or Component Type:
circuit breaker
Trip Unit Technology:
electronic, basic, ET 1.0,
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Quality Labels:
CE
Suitability For Isolation:
yes IEC 60947-2
Utilisation Category:
category A
Range:
PowerPact
Breaking Capacity:
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
Magnetic Tripping Current:
1200-6000 A
Pvc Free:
Yes
Mounting Mode:
unit mount lug)
Continuous Current Rating:
0.8
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Electrical Connection:
lugs, load || lugs, line
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Product Name:
PowerPact M
$11,427.00

Description

PowerPacT M-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT M-Frame circuit breakers have either a fixed long time electronic trip unit or an adjustable amperage version. This circuit breaker has an electronic trip unit, ET 1.0. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT M circuit breakers are available in 2 and 3-pole unit mount or I-Line construction. This unit has lugs on both the line and load sides. This PowerPacT M, 600A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. This unit includes a control wire terminal on the both ends. PowerPacT M circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose