- Pvc Free:
- Yes
- Range:
- PowerPact
- Local Signalling:
- 1 trip indicator green)
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- Circularity Profile:
- ENVEOLI2206030EN
- Color:
- Black
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Suitability For Isolation:
- yes IEC 60947-2
- Device Application:
- distribution
- Net Weight:
- 29 lb(US)
- Mounting Support:
- lug
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
- Sustainable Offer Status:
- Green Premium product
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Operation:
- -25-70 °C
- Product Name:
- PowerPact M
- Mounting Mode:
- unit mount lug)
- Product Or Component Type:
- circuit breaker
- Ambient Air Temperature For Storage:
- -50-85 °C
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Network Frequency:
- 50/60 Hz
- Poles Description:
- 3P
- Circuit Breaker Application:
- HACR rated
- Eu Rohs Directive:
- Compliant with Exemptions
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mercury Free:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Quantity Per Set:
- 1
- Wire Stripping Length:
- 25 mm
- Pollution Degree:
- 3 IEC 60947-1
- Quality Labels:
- CE
- Width:
- 8.27 in
- Control Type:
- operating handle
- Trip Unit Name:
- ET 1.0
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206030EN
- Magnetic Tripping Current:
- 1600-8000 A
- Rohs Exemption Information:
- Yes
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Electrical Connection:
- lugs, load || lugs, line
- Terminal Identifier:
- AL800M23K
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Depth:
- 8.05 in
- Ip Degree Of Protection:
- IP40
- Utilisation Category:
- category A
- Continuous Current Rating:
- 0.8
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Warranty:
- 18 months
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- Breaking Capacity Code:
- G
- Line Rated Current:
- 800-800 A
- Height:
- 12.86 in
- Product Certifications:
- UL || CSA || NOM