- Product Certifications:
- UL || CSA || NOM
- Ambient Air Temperature For Storage:
- -50-85 °C
- Control Type:
- operating handle
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Line Rated Current:
- 500-500 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Quality Labels:
- CE
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Mercury Free:
- Yes
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Rohs Exemption Information:
- Yes
- Ambient Air Temperature For Operation:
- -25-70 °C
- Mounting Support:
- lug
- Trip Unit Name:
- ET 1.0
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Suitability For Isolation:
- yes IEC 60947-2
- Width:
- 8.27 in
- Range:
- PowerPact
- Utilisation Category:
- category A
- Network Frequency:
- 50/60 Hz
- Warranty:
- 18 months
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Wire Stripping Length:
- 25 mm
- Height:
- 12.86 in
- Electrical Connection:
- lugs, load || lugs, line
- Environmental Disclosure:
- ENVPEP2206030EN
- Continuous Current Rating:
- 0.8
- Product Name:
- PowerPact M
- Ip Degree Of Protection:
- IP40
- Circularity Profile:
- ENVEOLI2206030EN
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Device Application:
- distribution
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Local Signalling:
- 1 trip indicator green)
- Mounting Mode:
- unit mount lug)
- Net Weight:
- 29 lb(US)
- Product Or Component Type:
- circuit breaker
- Color:
- Black
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- Eu Rohs Directive:
- Compliant with Exemptions
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Magnetic Tripping Current:
- 1000-5000 A
- Quantity Per Set:
- 1
- Breaking Capacity Code:
- J
- Depth:
- 8.05 in
- Pvc Free:
- Yes
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Poles Description:
- 3P
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
- Pollution Degree:
- 3 IEC 60947-1
- Terminal Identifier:
- AL800M23K
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating