- Control Type:
- operating handle
- Suitability For Isolation:
- yes IEC 60947-2
- Terminal Identifier:
- AL800M23K
- Circuit Breaker Application:
- HACR rated
- Line Rated Current:
- 300-800 A
- Ip Degree Of Protection:
- IP40
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Poles Description:
- 3P
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70 °C
- Device Application:
- distribution
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Height:
- 12.86 in
- Network Frequency:
- 50/60 Hz
- Mounting Support:
- lug
- Ambient Air Temperature For Storage:
- -50-85 °C
- Eu Rohs Directive:
- Compliant with Exemptions
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Environmental Disclosure:
- ENVPEP2206030EN
- Quantity Per Set:
- 1
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Range:
- PowerPact
- Pvc Free:
- Yes
- Product Or Component Type:
- circuit breaker
- Communication Interface:
- Modbus
- Wire Stripping Length:
- 25 mm
- Quality Labels:
- CE
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Mercury Free:
- Yes
- Electrical Connection:
- lugs, line || terminal nut, load
- Continuous Current Rating:
- 0.8
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Product Name:
- PowerPact M
- Width:
- 8.27 in
- Magnetic Tripping Current:
- 1600-8000 A
- Sustainable Offer Status:
- Green Premium product
- Net Weight:
- 29 lb(US)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Breaking Capacity Code:
- J
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- Utilisation Category:
- category A
- Accessory / Separate Part Type:
- communication module
- Rohs Exemption Information:
- Yes
- Product Certifications:
- UL || CSA || NOM
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
- Color:
- Black
- Local Signalling:
- 1 trip indicator green)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Mounting Mode:
- unit mount lug)
- Depth:
- 8.05 in
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Circularity Profile:
- ENVEOLI2206030EN
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Trip Unit Name:
- ET 1.0
- QN-QUOTE-REQUEST:
- true