- Trip Unit Name:
- MicroLogic 5.0
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Circularity Profile:
- ENVEOLI2206033EN
- Ambient Air Temperature For Storage:
- -50-85 °C
- Width:
- 8.27 in
- Control Type:
- toggle
- Phase Connection:
- ABC
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Ip Degree Of Protection:
- front cover IP40
- Height:
- 12.86 in
- Mounting Height:
- 9 in
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Trip Unit Technology:
- electronic, standard, MicroLogic 5.0, LSI
- Mounting Mode:
- I-Line bracket)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Terminal Identifier:
- AL800M23K
- Line Rated Current:
- 800-800 A
- Product Name:
- PowerPact P
- Network Frequency:
- 50/60 Hz
- Pvc Free:
- Yes
- Continuous Current Rating:
- 0.8
- Environmental Disclosure:
- ENVPEP2206033EN
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Poles Description:
- 3P
- Local Signalling:
- overload 1 1 LED amber) || 1 trip indicator green)
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Device Application:
- distribution
- Mounting Support:
- bracket
- Quantity Per Set:
- 1
- Rohs Exemption Information:
- Yes
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Net Weight:
- 32 lb(US)
- Product Or Component Type:
- circuit breaker
- Mercury Free:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Awg Gauge:
- 3 x AWG 3/0...500 kcmil aluminium/copper
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Wire Stripping Length:
- 25 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Ambient Air Temperature For Operation:
- -2-70 °C
- Range:
- PowerPact
- Circuit Breaker Application:
- HACR rated
- Electrical Connection:
- I-Line connection, line || lugs, load
- Breaking Capacity Code:
- G
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Quality Labels:
- CE
- Eu Rohs Directive:
- Compliant with Exemptions
- Warranty:
- 18 months
- Pollution Degree:
- 3 IEC 60947-1
- Depth: