Schneider Electric

Schneider Electric PGL36100 Molded Case Circuit Breaker 600V 1000A

(No reviews yet) Write a Review
SKU:
PGL36100
UPC:
785901787167
Condition:
New
Pollution Degree:
3 IEC 60947-1
Circuit Breaker Application:
HACR rated
Trip Unit Technology:
electronic, basic, ET 1.0I, I
Breaking Capacity:
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
Breaking Capacity Code:
G
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Product Name:
PowerPact P
Rohs Exemption Information:
Yes
Sustainable Offer Status:
Green Premium product
Electrical Connection:
lugs, load || lugs, line
Product Or Component Type:
circuit breaker
Depth:
8.05 in
Awg Gauge:
4 x AWG 3/0...500 kcmil aluminium/copper
Net Weight:
32 lb(US)
Ambient Air Temperature For Storage:
-50-85 °C
Quality Labels:
CE
Line Rated Current:
1000-1000 A
Terminal Identifier:
AL1200P25K
Warranty:
18 months
Continuous Current Rating:
0.8
Network Frequency:
50/60 Hz
Quantity Per Set:
1
Height:
16.16 in
Ip Degree Of Protection:
front cover IP40
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Range:
PowerPact
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Long Time Pick-Up Adjustment Range:
1 In
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Mercury Free:
Yes
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Eu Rohs Directive:
Compliant with Exemptions
Environmental Disclosure:
ENVPEP2206033EN
Product Certifications:
UL || CSA || NOM
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Tightening Torque:
50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
[Ics] Rated Service Breaking Capacity:
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
Ambient Air Temperature For Operation:
-2-70 °C
Circularity Profile:
ENVEOLI2206033EN
Pvc Free:
Yes
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Poles Description:
3P
Trip Unit Name:
ET 1.0I
Width:
8.27 in
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Local Signalling:
1 trip indicator green)
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Control Type:
toggle
Wire Stripping Length:
30 mm
Device Application:
distribution
Brochure:
View
Catalog:
View
Datasheet:
View
$19,049.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has an electronic trip unit, ET 1.0I. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 1000A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose