- Mounting Support:
- bracket
- Network Frequency:
- 50/60 Hz
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Mounting Height:
- 9 in
- Local Signalling:
- overload 1 trip indicator green) || 1 trip indicator green)
- Ambient Air Temperature For Operation:
- -2-70 °C
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Circularity Profile:
- ENVEOLI2206033EN
- Pollution Degree:
- 3 IEC 60947-1
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Continuous Current Rating:
- 0.8
- Control Type:
- toggle
- Awg Gauge:
- 3 x AWG 3/0...500 kcmil aluminium/copper
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mercury Free:
- Yes
- Terminal Identifier:
- AL800M23K
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Device Application:
- distribution
- Range:
- PowerPact
- Eu Rohs Directive:
- Compliant with Exemptions
- Electrical Connection:
- I-Line connection, line || lugs, load
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Net Weight:
- 32 lb(US)
- Phase Connection:
- ABC
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Sustainable Offer Status:
- Green Premium product
- Trip Unit Name:
- MicroLogic 3.0
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Warranty:
- 18 months
- Product Name:
- PowerPact P
- Height:
- 12.86 in
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- Product Certifications:
- UL || CSA || NOM
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Pvc Free:
- Yes
- Depth:
- 8.05 in
- Mounting Mode:
- I-Line bracket)
- Quantity Per Set:
- 1
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Wire Stripping Length:
- 25 mm
- Quality Labels:
- CE
- Product Or Component Type:
- circuit breaker
- Poles Description:
- 3P
- Breaking Capacity Code:
- J
- Environmental Disclosure:
- ENVPEP2206033EN
- Rohs Exemption Information:
- Yes
- Ambient Air Temperature For Storage:
- -50-85 °C
- Ip Degree Of Protection:
- front cover IP40
- Width:
- 8.27 in
- Circuit Breaker Application:
- HACR rated
- Line Rated Current:
- 250-250 A
- QN-QUOTE-REQUEST:
- true