Schneider Electric

Schneider Electric PJL36060U41A Circuit breaker, PowerPacT P, 600A, 3 pole, 600VAC, 25kA, lugs, Micrologic 3.0A, 80%

(No reviews yet) Write a Review
SKU:
PJL36060U41A
MPN:
PJL36060U41A
Condition:
New
Network Frequency:
50/60 Hz
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Poles Description:
3P
Eu Rohs Directive:
Compliant with Exemptions
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Pvc Free:
Yes
Electrical Connection:
lugs, line || lugs, load
Device Application:
distribution
Product Certifications:
UL || CSA || NOM
Wire Stripping Length:
25 mm
[Ics] Rated Service Breaking Capacity:
35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Mounting Support:
lug
Terminal Identifier:
AL800M23K
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Country of Origin:
United States
Length:
25 mm
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Circuit Breaker Application:
HACR rated
Continuous Current Rating:
0.8
Product Name:
PowerPact P
Ambient Air Temperature For Storage:
-50-85°C
Quality Labels:
CE
Range:
PowerPact
Ip Degree Of Protection:
front cover IP40
Mercury Free:
Yes
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Trip Unit Technology:
electronic, ammeter, MicroLogic 3.0 A, LI
Ambient Air Temperature For Operation:
-25-70°C
Trip Unit Name:
MicroLogic 3.0 A
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Warranty:
18 months
Quantity Per Set:
1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Weight:
32 lb(US)
Mounting Mode:
unit mount lug)
Product Or Component Type:
circuit breaker
Breaking Capacity Code:
J
Rohs Exemption Information:
Yes
Line Rated Current:
600-600 A
$16,421.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Ammeter with a 3.0A trip unit and an LI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 600A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose