Schneider Electric PJL36080U33A Molded Case Circuit Breaker 600V 800A

(No reviews yet) Write a Review
SKU:
PJL36080U33A
UPC:
3606489640446
Condition:
New
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Width:
8.27 in
Poles Description:
3P
Pvc Free:
Yes
Depth:
8.05 in
[Ics] Rated Service Breaking Capacity:
35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
Product Certifications:
UL || CSA || NOM
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Ambient Air Temperature For Storage:
-50-85 °C
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Ambient Air Temperature For Operation:
-2-70 °C
Terminal Identifier:
AL800M23K
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Product Name:
PowerPact P
Sustainable Offer Status:
Green Premium product
Rohs Exemption Information:
Yes
Line Rated Current:
800-800 A
Pollution Degree:
3 IEC 60947-1
Warranty:
18 months
Mercury Free:
Yes
Local Signalling:
overload 1 1 LED amber) || 1 trip indicator green)
Trip Unit Technology:
electronic, standard, MicroLogic 5.0, LSI
Height:
12.86 in
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Eu Rohs Directive:
Compliant with Exemptions
Breaking Capacity Code:
J
Control Type:
toggle
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Trip Unit Name:
MicroLogic 5.0
Range:
PowerPact
Circuit Breaker Application:
HACR rated
Ip Degree Of Protection:
front cover IP40
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Quality Labels:
CE
Quantity Per Set:
1
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Network Frequency:
50/60 Hz
Wire Stripping Length:
25 mm
Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
Electrical Connection:
lugs, line || lugs, load
Product Or Component Type:
circuit breaker
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Mounting Support:
lug
Net Weight:
32 lb(US)
Mounting Mode:
unit mount lug)
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Environmental Disclosure:
ENVPEP2206033EN
Circularity Profile:
ENVEOLI2206033EN
Continuous Current Rating:
0.8
Device Application:
distribution
$15,909.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard with a 5.0 trip unit and an LSI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 800A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.