- Poles Description:
- 3P
- Mercury Free:
- Yes
- Circuit Breaker Application:
- HACR rated
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Length:
- 30 mm
- Wire Stripping Length:
- 30 mm
- Rohs Exemption Information:
- Yes
- Local Signaling:
- overload 1 1 LED amber) || 1 flag green) || trip causes 4 trip indicator red)
- Quality Labels:
- CE
- Awg Gauge:
- 4 x AWG 3/0...500 kcmil aluminium/copper
- Terminal Identifier:
- AL1200P25K
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Height:
- 16.16 in
- Weight:
- 32 lb(US)
- Ip Degree Of Protection:
- front cover IP40
- Utilisation Category:
- category A
- Product Certifications:
- UL || CSA || NOM
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Pollution Degree:
- 3 IEC 60947-1
- Ambient Air Temperature For Operation:
- -25-70°C
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Circularity Profile:
- ENVEOLI2206033EN
- Breaking Capacity Code:
- J
- Range:
- PowerPact
- Net Weight:
- 32 lb(US)
- Warranty:
- 18 months
- Mounting Support:
- lug
- Product Name:
- PowerPact P
- Line Rated Current:
- 1200-1200 A
- Ambient Air Temperature For Storage:
- -50-85°C
- Electrical Connection:
- lugs, line || lugs, load
- Control Type:
- toggle
- Network Frequency:
- 50/60 Hz
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Depth:
- 8.05 in
- Suitability For Isolation:
- yes IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Device Application:
- distribution
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Country of Origin:
- Mexico
- Eu Rohs Directive:
- Compliant with Exemptions
- Environmental Disclosure:
- ENVPEP2206033EN
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Continuous Current Rating:
- 0.8
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Quantity Per Set:
- 1