- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Or Component Type:
- circuit breaker
- Environmental Disclosure:
- ENVPEP2206033EN
- Poles Description:
- 3P
- Ambient Air Temperature For Operation:
- -2-70 °C
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- Local Signalling:
- overload 1 1 LED amber) || 1 trip indicator green)
- Height:
- 16.16 in
- Continuous Current Rating:
- 0.8
- Mounting Mode:
- unit mount lug)
- Quantity Per Set:
- 1
- Pollution Degree:
- 3 IEC 60947-1
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Pvc Free:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Warranty:
- 18 months
- Circularity Profile:
- ENVEOLI2206033EN
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Device Application:
- distribution
- Quality Labels:
- CE
- Net Weight:
- 32 lb(US)
- Awg Gauge:
- 4 x AWG 3/0...500 kcmil aluminium/copper
- Ip Degree Of Protection:
- front cover IP40
- Sustainable Offer Status:
- Green Premium product
- Ambient Air Temperature For Storage:
- -50-85 °C
- Product Certifications:
- UL || CSA || NOM
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Product Name:
- PowerPact P
- Mounting Support:
- lug
- Terminal Identifier:
- AL1200P25K
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Tightening Torque:
- 50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Network Frequency:
- 50/60 Hz
- Rohs Exemption Information:
- Yes
- Range:
- PowerPact
- Wire Stripping Length:
- 30 mm
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Trip Unit Name:
- MicroLogic 3.0
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Eu Rohs Directive:
- Compliant with Exemptions
- Circuit Breaker Application:
- HACR rated
- Control Type:
- toggle
- Electrical Connection:
- terminal nut, line || lugs, load
- Line Rated Current:
- 1200-1200 A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Depth:
- 8.05 in
- Breaking Capacity Code:
- J
- Width:
- 8.27 in
- Mercury Free:
- Yes
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- QN-QUOTE-REQUEST:
- true