- Network Frequency:
- 50/60 Hz
- Control Type:
- operating handle
- Height:
- 6.47 in
- Product Name:
- PowerPact Q
- Warranty:
- 18 months
- Electrical Connection:
- lugs, load || lugs, line
- Ambient Air Temperature For Operation:
- 40-70 °C
- Pvc Free:
- Yes
- Wire Stripping Length:
- 22 mm
- Circularity Profile:
- N/A
- Local Signalling:
- 1 trip indicator green)
- Mounting Support:
- lug
- Halogen Content Performance:
- Halogen free product
- Product Or Component Type:
- circuit breaker
- Eu Rohs Directive:
- Compliant with Exemptions
- Breaking Capacity:
- 100 kA 120/208 V AC 50/60 Hz UL
- Mounting Mode:
- unit mount lug)
- Width:
- 4.5 in
- Magnetic Tripping Current:
- 2400-2400 A
- Rohs Exemption Information:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Trip Unit Technology:
- thermal-magnetic
- Poles Description:
- 3P
- Range:
- PowerPact
- Magnetic Hold Current:
- 1200 A
- Mercury Free:
- Yes
- Device Application:
- distribution
- Utilisation Category:
- category A
- Sustainable Offer Status:
- Green Premium product
- [Ue] Rated Operational Voltage:
- 240 V AC 50/60 Hz UL
- Environmental Disclosure:
- ENVPEP1406032EN
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Line Rated Current:
- 225 A
- Line Rated Current:
- 225-225 A
- Product Certifications:
- UL || CSA || NOM
- Continuous Current Rating:
- 0.8
- Tightening Torque:
- 28-28 N.m 25-150 mm² (AWG 4...300 kcmil)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Depth:
- 3.93 in
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV UL
- Breaking Capacity Code:
- J
- Mechanical Durability:
- 1000 cycles loaded || 5000 cycles no load
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000
- QN-QUOTE-REQUEST: