- Relay Type:
- temperature control relays
- Relay Name:
- RM35AT
- Time Delay Range:
- 0.1...10 s adjustable 0...10 % of the full scale value)
- [Ui] Rated Insulation Voltage:
- 250 V IEC 60664-1
- Shock Resistance:
- 15 gn 11 ms IEC 60255-21-1
- Electromagnetic Compatibility:
- emission standard for industrial environments IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments IEC 61000-6-3 || immunity for industrial environments NF EN/IEC 61000-6-2
- Standards:
- IEC 60255-6 || NF EN 60255-6
- Product Or Component Type:
- elevator machine room temperature control relay
- Sustainable Offer Status:
- Green Premium product
- Resistance Across Terminals:
- 1.33 kOhm temperature
- Operating Rate:
- <= 360 operations/hour full load
- Insulation Resistance:
- > 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || > 500 MOhm 500 V DC between supply and relay ou
- China Rohs Regulation:
- X
- Insulation:
- galvanic insulation between supply and measurement
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Non-Dissipating Shock Wave:
- 4 kV
- Temperature Probe Type:
- Pt 100 - 3-wire
- [Us] Rated Supply Voltage:
- 24...240 V AC/DC
- Environmental Disclosure:
- ENVPEP1504008EN
- Product Specific Application:
- for elevator machine rooms and 3-phase supplies
- Warranty:
- 18 months
- Pollution Degree:
- 3 IEC 60664-1
- Measurement Accuracy:
- +/- 2 °C
- Ambient Air Temperature For Storage:
- -40-70 °C
- Width:
- 35 mm
- Dielectric Test Voltage:
- 2 kV AC 50 Hz, 1 min
- Vibration Resistance:
- 0.35 mm 5-57.6 Hz)IEC 60068-2-6/IEC 60255-21-1 || 1 gn 57.6-150 Hz)IEC 60068-2-6/IEC 60255-21-1
- Marking:
- CE : EMC 89/336/EEC || CE : 73/23/EEC
- Maximum Switching Voltage:
- 250 V AC/DC
- Ambient Air Temperature For Operation:
- -20-50 °C
- Circularity Profile:
- ENVEOLI1504008EN
- Installed Device:
- Pt 100 probe cable length <= 10 m
- Range Of Product:
- Harmony Control Relays
- Control Circuit Voltage Limits:
- 10 % + 10 % Un DC || - 15 % + 10 % Un AC
- Nominal Output Current:
- 0.208333333333333
- Response Time:
- <= 3.5 s + Tt (in case of temperature fault) || <= 3.5 s (on disappearance of fault)
- Rohs Exemption Information:
- Yes
- Run-Up Delay At Power-Up:
- 0.2 s
- Supply Frequency:
- 50/60 Hz +/- 10 %
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Relay Monitored Parameters:
- undertemperature: -1...11°C || overtemperature: 34...46°C
- Overvoltage Category:
- III IEC 60664-1
- Reset Time:
- 8 s
- Mounting Support:
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Connections - Terminals:
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end ||
- Product Certifications:
- GOST || GL || C-tick || UL || CSA
- Housing Material:
- self-extinguishing plastic
- Status Led:
- 1 LED Green power ON || 1 LED Yellow correct temperature (high R1) || 1 LED Yellow correct temperature (low R2)
- Immunity To Microbreaks:
- 10 ms
- Ip Degree Of Protection:
- IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
- Maximum Power Consumption In W:
- 0.6 W DC
- Mechanical Durability:
- 30000000 cycles
- Operating Position:
- any position without derating
- Utilisation Category:
- AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || DC-14 IEC 60947-5-1
- Contacts Material:
- cadmium free
- Maximum Power Consumption In Va:
- 3.5 VA AC
- Electrical Durability:
- 100000 cycles
- Control Type:
- without test button
- Output Contacts:
- 1 C/O
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mercury Free:
- Yes
- Measurement Range:
- +/- 1...46 °C
- Switching Capacity In Va:
- 1250 VA
- Minimum Switching Current:
- 10 mA 5 V DC
- Supply Voltage Limits:
- 20.4-264 V AC || 21.6-264 V DC
- Tightening Torque:
- 0.6-1 N.m IEC 60947-1
- QN-QUOTE-REQUEST:
- true