Analogue Output Current:
-30-0 mA no input or input wire broken || 22-30 mA no input or input wire broken
Measurement Error:
+/- 0.5 % of full scale 3 or 4 wires)20 °C || +/- 1 % of full scale 2 wires)20 °C || +/- 10 % of full scale20 °C electromagnetic interference of 10 V/m)
Circularity Profile:
ENVEOLI1607005EN
Analogue Output Type:
current 4...20 mA <= 500 Ohm || voltage 0...10 V >= 100 kOhm
Maximum Wiring Resistance:
0.2 Ohm 2 wires
[Us] Rated Supply Voltage:
24 V DC non isolated +/- 20 %
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Repeat Accuracy:
+/- 0.2 % full scale 20 °C || +/- 0.6 % full scale 60 °C
Surge Withstand:
0.5 kV 1.2/50 µs IEC 61000-4-5
Environmental Disclosure:
ENVPEP1607005EN
Product Certifications:
UL || GL || CSA
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Shock Resistance:
50 gn 11 ms IEC 60068-2-27
Tightening Torque:
0.6-1.1 N.m
Fixing Mode:
clip-on 35 mm symmetrical DIN rail) || fixed mounting plate)
Standards:
DIN 43760 || EN/IEC 60584-1 || EN/IEC 60751 || EN/IEC 60947-1
Net Weight:
0.12 kg
Product Or Component Type:
converter for Optimum Pt100 probes
Warranty:
18 months
Ambient Air Temperature For Operation:
0-50 °C mounting side by side || 0-60 °C 2 cm spacing
Clamping Connection Capacity:
2 x 1.5 mm² || 1 x 2.5 mm²
Resistance To Fast Transients:
1 kV IEC 61000-4-4 on input-output) || 2 kV IEC 61000-4-4 on power supply)
Vibration Resistance:
5 gn 10-100 Hz)IEC 60068-2-6
Rohs Exemption Information:
Yes
China Rohs Regulation:
X
Analogue Output Voltage:
-15...-11 V no input or input wire broken || 11...15 V no input or input wire broken
Pollution Degree:
2 IEC 60664-1
Temperature Coefficient:
150 ppm/°C
Disturbance Radiated/Conducted:
CISPR 22 group 1 - class B || CISPR 11
Local Signalling:
for power ON LED (green)
Electromagnetic Compatibility:
electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 || electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Fire Resistance:
850 °C IEC 60695-2-1 || 850 °C UL
Ambient Air Temperature For Storage:
-40-85 °C
Marking:
CE
Analogue Input Type:
temperature probe 0...100 °C/32..212 °F Pt 100 2, 3 or 4 wires
[Ui] Rated Insulation Voltage:
2000 V
Current Consumption:
<= 40 mA voltage output || <= 60 mA current output
Range Of Product:
Harmony Analog
Sustainable Offer Status:
Green Premium product
Protection Type:
short-circuit protection on output || reverse polarity protection on output || overvoltage protection on output (+/- 30 V) || reverse polarity protection on power supply
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Ip Degree Of Protection:
IP20 terminal block) || IP50 housing)
Safety Reliability Data:
MTTFd = 43.9 years || B10d = 40564
California Proposition 65:
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other repr
Mercury Free:
Yes
  • Schneider Electric RMPT33BD Harmony Analogue Pt100 0-100C
  • Schneider Electric RMPT33BD Harmony Analogue Pt100 0-100C
  • Schneider Electric RMPT33BD Harmony Analogue Pt100 0-100C
$113.00

Description

This temperature transmitter is part of the range of Harmony Analog interfaces. It is designed to convert signal of Pt100 probe into standard electrical signal which is compatible with automation platforms, controllers. Its supply voltage is 24V DC, non isolated. It also allows the connection distance between a sensor and the measurement acquisition device to be increased. The cables used to connect the converters to process equipment (PLCs) are standard cables, which are more cost effective than extension cables or compensation cables suitable for low level signals for Pt100 probes or thermocouples. Conforming to IEC standards, UL and CSA certified, this converter is suitable for universal use. 0 0 0 0 0 0 0 0 0 0