Schneider Electric RPM32BD 15A Power Relay Led 3C/O 24Vdc Pack of 10
Schneider Electric
$109.80
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
This Harmony RPM power plug-in relay has a coil control voltage of 24V DC and has 3 changeover contacts 3PDT (triple pole double throw) with a rating of 15A. It has large choice of number of contacts for high rated current use. It also offers LED indicator to alert on the current status of the relay. It helps to reduce the size of enclosures and increase machine reliability, you can mount nearly everywhere. This RPM product is IP40. Workability for hard-wired logic automated systems to complement the functions of industrial programmable logic controllers (PLCs). Status display with LED, clearly signal both in the day and night. 0 0 0 0 0 0 0 0 0
- China Rohs Regulation:
- X
- Range Of Product:
- Harmony Electromechanical Relays
- Pollution Degree:
- 3
- Product Certifications:
- EAC || UL || CSA
- Safety Reliability Data:
- B10d = 100000
- Sustainable Offer Status:
- Green Premium product
- Device Short Name:
- RPM
- Maximum Switching Capacity:
- 3750 VA || 420 W
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV 1.2/50 µs
- Contacts Type And Composition:
- 3 C/O
- Product Or Component Type:
- plug-in relay
- Load Current:
- 15 A 250 V AC || 15 A 28 V DC
- [Ui] Rated Insulation Voltage:
- 250 V IEC || 300 V CSA || 300 V UL
- Shape Of Pin:
- flat
- Shock Resistance:
- 15 gnin operation || 30 gnnot operating
- Contacts Material:
- AgNi
- Ambient Air Temperature For Storage:
- -40-85 °C
- Ip Degree Of Protection:
- IP40 conforming to IEC 60529
- Utilisation Coefficient:
- 0.2
- Minimum Switching Capacity:
- 170 mW 10 mA, 17 V
- Operating Position:
- any position
- [Ie] Rated Operational Current:
- 15 A 277 V AC) UL || 15 A 28 V DC) UL || 15 A 250 V AC) NO IEC || 15 A 28 V DC) NO IEC || 7.5 A 250 V AC) NC IEC || 7.5 A 28 V DC) NC IEC
- Control Type:
- lockable test button
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other repr
- Standards:
- UL 508 || CSA C22.2 No 14 || IEC 61810-1
- Operating Rate:
- <= 1200 cycles/hour under load || <= 18000 cycles/hour no-load
- Reset Time:
- 20 ms at nominal voltage
- [Uc] Control Circuit Voltage:
- 24 V DC
- [Ithe] Conventional Enclosed Thermal Current:
- 15 A -40-55 °C
- Vibration Resistance:
- 3 gn +/- 1 mm 10-150 Hz)5 cycles in operation || 5 gn +/- 1 mm 10-150 Hz)5 cycles not operating
- Average Resistance:
- 320 Ohm at 20 °C +/- 10 %
- Protection Category:
- RT I
- Device Presentation:
- complete product
- Mechanical Durability:
- 10000000 cycles
- Rohs Exemption Information:
- Yes
- Series Name:
- Power
- Environmental Disclosure:
- ENVPEP1406038EN
- Status Led:
- with
- Warranty:
- 18 months
- Electrical Durability:
- 100000 cycles resistive
- Drop-Out Voltage Threshold:
- >= 0.1 Uc DC
- Operating Time:
- 20 ms at nominal voltage
- Maximum Switching Voltage:
- 250 V IEC
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Circularity Profile:
- N/A
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Dielectric Strength:
- 1500 V AC between contacts with micro disconnection || 2000 V AC between coil and contact with reinforced || 2000 V AC between poles with basic
- Reach Free Of Svhc:
- Yes
- Net Weight:
- 0.054 kg
- Rated Operational Voltage Limits:
- 19.2...26.4 V DC
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Test Levels:
- level A group mounting
- Ambient Air Temperature For Operation:
- -40-55 °C
- Average Coil Consumption:
- 1.5 W
- Catalog:
- View
- Datasheet:
- View