Schneider Electric STBDDO3605K 24Vdc Out 6Pt Basic Kit Conns,Base
Schneider Electric
$123.00
digital output kit, Modicon STB, basic, 24V DC, 6 O
- Supply:
- power distribution module
- Kit Composition:
- STBDDO3605 module || STBXTS2100, 6-terminal spring clamp connector || STBXBA1000 base || STBXTS1100, 6-terminal screw type connector
- Discrete Output Logic:
- positive
- Product Compatibility:
- I/O base STBXBA1000 || power distribution module STBPDT3100/3105
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Ambient Air Temperature For Storage:
- -40...185 °F without derating
- Pollution Degree:
- 2 IEC 60664-1
- Maximum Load Capacitance:
- 50 µF
- Current Consumption:
- 90 mA 5 V DC logic bus
- Standards:
- IEC 61131-2
- Ambient Air Temperature For Operation:
- 32...140 °F without derating
- Operating Altitude:
- <= 6561.68 ft (2000 m)
- Discrete Output Current:
- 250 mA
- Shock Resistance:
- 30 gn 11 ms IEC 88 reference 2-27
- Hot Swapping Fallback:
- no for basic NIMs
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mercury Free:
- Yes
- Discrete Output Number:
- 6
- Range Of Product:
- Modicon STB distributed I/O solution
- Vibration Resistance:
- 3 gn 58-150 Hz 35 x 7.5 mm symmetrical DIN rail || 5 gn 58-150 Hz 35 x 15 mm symmetrical DIN rail || +/-0.35 mm 10-58 Hz
- Rohs Exemption Information:
- Yes
- Marking:
- CE
- Ambient Air Temperature For Storage:
- -40-85 °C without derating
- Warranty:
- 18 months
- Discrete Output Type:
- solid state
- Status Led:
- 1 LED (Green) module status (RDY) || 1 LED per channel (Green) channel status (OUT1 to OUT6)
- Surge Current:
- 2.5 A 0.5 ms
- Ambient Air Temperature For Operation:
- 0-60 °C without derating)
- Cold Swapping:
- yes
- Insulation Between Channels And Logic Bus:
- 1500 V for 1 minute
- Ip Degree Of Protection:
- IP20 conforming to IEC 61131-2 class 1
- Output Voltage:
- 19.2...30 V DC
- Height:
- 13.9 mm
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Depth:
- 70 mm
- Reset:
- manual or automatic reset COM fault
- Product Or Component Type:
- basic digital output kit
- Product Certifications:
- UL || CSA || FM Class 1 Division 2
- Discrete Output Voltage Type:
- DC
- Maximum Leakage Current:
- 0.4 mA at state 0 30 V
- Maximum Load Inductance:
- 500 mH 4 Hz
- Discrete Output Voltage:
- 24 V
- Response Time:
- 550 µs off-to-on || 900 µs on-to-off
- China Rohs Regulation:
- X
- Relative Humidity:
- 95-95 % 60-60 °C without condensation
- Absolute Maximum Voltage:
- 56 V 1.3 ms
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Protection Type:
- power protection integrated fuse on PDM time lag 5 A || reverse polarity protection || short-circuit protection || thermal overload protection
- [Us] Rated Supply Voltage:
- 24 V DC
- Overvoltage Category:
- II
- Width:
- 128.3 mm
- Net Weight:
- 0.114 kg
- Catalog:
- View
- Datasheet: