- Motor Starter Type:
- direct on line
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz
- Mounting Mode:
- horizontal and vertical 35 mm symmetrical DIN rail)
- Tightening Torque:
- 5-5 N.m 1-25 mm² hexagonal 4 mm || 8-8 N.m 25-35 mm² hexagonal 4 mm
- [Ith] Conventional Free Air Thermal Current:
- 80 A (at 50°C)
- [Ie] Rated Operational Current:
- 66 A (at <50°C) at <= 440 V AC-3 || 80 A (at <50°C) at <= 440 V AC-1
- Eu Rohs Directive:
- Compliant with Exemptions
- Net Weight:
- 1.248 kg
- Connections - Terminals:
- EverLink BTR screw connectors 1 1-35 mm² AWG 16...AWG 2)rigid || EverLink BTR screw connectors 2 1-25 mm² AWG 16...AWG 4)rigid || EverLink BTR screw connectors 1 1-35 mm² AWG 16...AWG 2)flexible without cable end || EverLink BTR screw connector
- Device Presentation:
- direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
- Local Signaling:
- for DS (device status) 1 LED (green/red) || for LS (load status) 1 LED (green/red)
- Operating Altitude:
- 0...6561.68 ft (0...2000 m) without derating
- Overvoltage Category:
- III
- Power Dissipation Per Pole:
- 6.5 W AC-3 || 9.6 W AC-1
- Thermal Protection Adjustment Range:
- 4-80 A
- Mechanical Durability:
- 6 Mcycles
- Country of Origin:
- Mexico
- Rated Breaking Capacity:
- 1000 A at 440 V conforming to IEC 60947
- Utilisation Category:
- AC-1 || AC-2 || AC-3 || AC-4 || AC-3e
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947-1
- Shock Resistance:
- 15 gn 11 ms) IEC 60068-2-27
- Protective Treatment:
- TC
- Safety Level:
- SIL 2 conforming to IEC 61508 in single channel system architecture || SILCL 2 conforming to IEC 62061 in single channel system architecture || PL = d category 2 conforming to ISO 13849-1 in single channel system architecture
- Poles Description:
- 3P 3 NO
- Reset:
- remotely or automatically
- Product Compatibility:
- TPRBC bus coupler || TPRVM voltage interface module || TPRSM SIL interface module
- Product Certifications:
- CSA || CCC || UL || EAC
- Current Consumption:
- 80 mA contactor sealed || 500 mA contactor closing
- Ambient Air Temperature For Operation:
- -10-50°C without derating || 50-60°C with current derating
- Maximum Operating Rate:
- 3600 cyc/mn AC-3
- Operating Time:
- < 80 ms closing || < 80 ms opening
- Thermal Overload Class:
- class 5…30
- Fire Resistance:
- 960°C UL 94 || 850°C IEC 60695-2-1 || 650°C IEC 60695-2-12
- Product Name:
- TeSys island
- [Ui] Rated Insulation Voltage:
- 690 V IEC 60947-4-1 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
- Protection Type:
- thermal overload protection || motor overheat || overcurrent || undercurrent || jam || long start || stall || rapid cycle lockout || phase sequence || rapid restart lockout || phase loss || phase reversal || phase unbalance || ground current
- Function Available:
- upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module || safe stop function available when connected with a TPRSM module
- [Icw] Rated Short-Time Withstand Current:
- 900 A 40°C - 1 s || 520 A 40°C - 10 s || 260 A 40°C - 1 min || 110 A 40°C - 10 min
- Environmental Disclosure:
- ENVPEP1904009EN
- Safety Function:
- safe stop: category 0 conforming to IEC 60204-1 when associated with a TPRSM module || safe stop: category 1 conforming to IEC 60204-1 when associated with a TPRSM module
- [Ue] Rated Operational Voltage:
- <= 690 V AC 47...63 Hz
- Irms Rated Making Capacity:
- 1000 A at 440 V conforming to IEC 60947
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Motor Power Kw:
- 18.5 kW at 230 V 50 Hz (AC-3) || 37 kW at 380...415 V 50 Hz (AC-3) || 37 kW at 440 V 50 Hz (AC-3) || 37 kW at 500 V 50 Hz (AC-3) || 37 kW at 690 V 50 Hz (AC-3)
- Ip Degree Of Protection:
- IP20