- Weight:
- 1.248 kg
- Product Certifications:
- UL || CSA || CCC || EAC
- Local Signaling:
- for DS (device status) 1 LED (green/red) || for LS (load status) 1 LED (green/red)
- Electromagnetic Compatibility:
- electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transient immunity test, level 4, 4 kV, conforming to E
- Maximum Horse Power Rating:
- 5 hp at 120 V AC 60 Hz for 1 phase motors || 10 hp at 240 V AC 60 Hz for 1 phase motors || 20 hp at 208 V AC 60 Hz for 3 phase motors || 20 hp at 240 V AC 60 Hz for 3 phase motors || 40 hp at 480 V AC 60 Hz for 3 phase motors || 50 hp at 600 V AC 60
- Rohs Exemption Information:
- Yes
- Overvoltage Category:
- III
- Product Or Component Type:
- motor starter
- Power Dissipation In W:
- 21.4 W at Ie AC-3
- Rated Breaking Capacity:
- 1000 A at 440 V conforming to IEC 60947
- Power Dissipation Per Pole:
- 6.5 W AC-3 || 9.6 W AC-1
- Relative Humidity:
- 5-95 %
- Maximum Operating Rate:
- 3600 cyc/mn AC-3
- Warranty:
- 18 months
- Irms Rated Making Capacity:
- 1000 A at 440 V conforming to IEC 60947
- Motor Power Kw:
- 18.5 kW at 230 V 50 Hz (AC-3) || 37 kW at 380...415 V 50 Hz (AC-3) || 37 kW at 440 V 50 Hz (AC-3) || 37 kW at 500 V 50 Hz (AC-3) || 37 kW at 690 V 50 Hz (AC-3)
- Poles Description:
- 3P 3 NO
- Electrical Durability:
- 0.75 Mcycles 66 A AC-3 440 V || 0.5 Mcycles 80 A AC-1 440 V
- Ambient Air Temperature For Storage:
- -25-70°C
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- [Ue] Rated Operational Voltage:
- <= 690 V AC 47...63 Hz
- [Ie] Rated Operational Current:
- 66 A (at <50°C) at <= 440 V AC-3 || 80 A (at <50°C) at <= 440 V AC-1
- Country of Origin:
- France
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Circularity Profile:
- ENVEOLI1904009EN
- [Ui] Rated Insulation Voltage:
- 690 V IEC 60947-4-1 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
- [Icw] Rated Short-Time Withstand Current:
- 900 A 40°C - 1 s || 520 A 40°C - 10 s || 260 A 40°C - 1 min || 110 A 40°C - 10 min
- Shock Resistance:
- 15 gn 11 ms) IEC 60068-2-27
- Fire Resistance:
- 960°C UL 94 || 850°C IEC 60695-2-1 || 650°C IEC 60695-2-12
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz
- Current Consumption:
- 80 mA contactor sealed || 500 mA contactor closing
- Product Compatibility:
- TPRBC bus coupler || TPRVM voltage interface module
- Eu Rohs Directive:
- Compliant with Exemptions
- Device Presentation:
- direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
- Thermal Overload Class:
- class 5…30
- Vibration Resistance:
- 1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
- Tightening Torque:
- 5-5 N.m 1-25 mm² hexagonal 4 mm || 8-8 N.m 25-35 mm² hexagonal 4 mm
- Motor Starter Type:
- direct on line
- Operating Altitude:
- 0...6561.68 ft (0...2000 m) without derating
- Function Available:
- upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module
- Sustainable Offer Status:
- Green Premium product
- Ip Degree Of Protection:
- IP20
- [Uc] Control Circuit Voltage:
- 24 V DC supplied by the bus coupler
- Utilisation Category:
- AC-1 || AC-2 || AC-3 || AC-4 || AC-3e
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947-1
- Pollution Degree:
- 2