Schneider Electric XPSMCMRO0004DAG 4 Safety Relay Outputs Exp. Spring Term

(No reviews yet) Write a Review
SKU:
XPSMCMRO0004DAG
UPC:
3.60648E+12
Condition:
New
Product Certifications:
TÜV || RCM || cULus
Shock Resistance:
10 gn 16 ms 1000 shocks on each axis)IEC 61496-1
[Uimp] Rated Impulse Withstand Voltage:
4 kV IEC 61800-5-1
Output Type:
relay, 4 NO, volt-free
Depth:
114.5 mm
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Local Signalling:
1 LED green PWR power ON || 1 LED green RUN RUN (status) || 1 LED red E IN internal error || 1 LED red E EX external error || 2 LEDs orange ADDR node address || 4 LEDs green/red RELAY K1...K4 relay contact || 4 LEDs yellow RST requires reset || 8 LED
Device Short Name:
XPSMCM
Number Of Terminal Blocks:
6
Reach Free Of Svhc:
Yes
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Range Of Product:
Preventa Safety automation
Ambient Air Temperature For Operation:
-10-55 °C
Safety Reliability Data:
B10d = 300000 AC-15 230 V, , <3 A ISO 13849-1 || B10d = 750000 AC-15 230 V, , <1 A ISO 13849-1 || B10d = 10000000 DC-13 24 V, , <2 A ISO 13849-1
Safety Level:
can reach category 4 ISO 13849-1 || can reach PL = e ISO 13849-1 || can reach SIL 3 IEC 61508 || SILCL 3 IEC 62061
Standards:
ISO 13849-1 || IEC 62061 || IEC 61800-5-1 || IEC 61508
Maximum Switching Current:
0.25
Quantity Per Set:
1
Quality Labels:
CE
Circularity Profile:
ENVEOLI1409010EN
Cable Cross Section:
0.2-2.5 mm² - AWG 24...AWG 14 flexible without cable end || 0.25-2.5 mm² - AWG 23...AWG 14 flexible with cable end, with bezel || 0.25-2.5 mm² - AWG 23...AWG 14 flexible with cable end, without bezel || 0.2-2.5 mm² - AWG 24...AWG 14 solid without
Rohs Exemption Information:
Yes
Ip Degree Of Protection:
IP20
Electromagnetic Compatibility:
electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to IEC 61000-4-2 || electrostatic discharge immunity test - test level: 20 kV (on air) conforming to IEC 61000-4-2 || susceptibility to electromagnetic fields - test lev
Associated Fuse Rating:
3.5 A, slow-blow
Height:
99 mm
Minimum Switching Current:
20 mA
Mounting Support:
omega 35 mm DIN rail EN 50022
Overvoltage Category:
II
Relative Humidity:
10-95 %
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Pollution Degree:
2
Vibration Resistance:
+/-0.35 mm 10-55 Hz)IEC 61496-1
Insulation:
250 V AC between power supply and housing IEC 61800-5-1
Mechanical Durability:
20000000 cycles
Maximum Switching Voltage:
400 V AC || 250 V DC
Integrated Connection Type:
backplane expansion bus
Electrical Durability:
20000000 cycles
Mercury Free:
Yes
Width:
22.5 mm
[Us] Rated Supply Voltage:
24 V - 20...20 % DC
Service Life:
20 year(s)
Ambient Air Temperature For Storage:
-20-85 °C
Pvc Free:
Yes
Discrete Output Number:
8-8 solid state 125 mA diagnostics)
Function Of Module:
monitoring safety actuators relay output
Sustainable Offer Status:
Green Premium product
Maximum Power Dissipation In W:
3 W
Number Of Outputs:
4 relay
Switching Voltage:
10 V DC
Connections - Terminals:
1 spring clamp terminals, removable terminal block || 2 spring clamp terminals, removable terminal block
Environmental Disclosure:
ENVPEP1409010EN
Switching Time:
12 ms
Reach Regulation:
Free of Substances of Very High Concern above the threshold
China Rohs Regulation:
X
Electrical Connection:
spring terminal
Net Weight:
0.33 kg
Product Or Component Type:
safe relay output module
Catalog:
View
Datasheet:
View
  • Schneider Electric XPSMCMRO0004DAG 4 Safety Relay Outputs Exp. Spring Term
  • Schneider Electric XPSMCMRO0004DAG 4 Safety Relay Outputs Exp. Spring Term
$754.00

Description

The safe relay output module provides 4 outputs and 8 solid state at 125mA (diagnostics) discrete outputs. It is designed to monitor safety actuators for relay outputs, with a rated supply voltage of 24V DC and a maximum power dissipation of 3W. It is furnished with spring clamp terminals, removable terminal block for electrical connection. It is an IP20 rated product. The safe relay modules type XPSMCMER0004 use guided contact safety relays, each of which provides two N.O. contacts and one N.C. contact in addition to the N.C. feedback contact. This safe relay output expansion module figures LEDs on its front face, displaying the status (power supply, run, internal or external errors, inputs status, restart signal, output channels). The safe relay output modules type XPSMCMER0002 and XPSMCMER0004 do not require the backplane expansion connectors as they are directly wired to the selected OSSD. It weighs 0.3kg. Its dimension are 22.5mm (Depth), 99mm (Height) and 114.5mm (Width). Its housing is red. It is powered with 24 VDC. It is ideal for monitoring safety functions such as emergency stop, guard monitoring, perimeter guarding, position monitoring, speed monitoring and enabling movement. The safe controller CPU Modicon MCM are certified by TüV SÜD meeting the industrial safety standards of Category 4, PL e according to EN/ISO 13849-1 and SILCL 3 according to IEC/EN 61508 and IEC/EN 60261. Compatible accessory for safe relay output module is a memory card. The module instals on Omega 35mm DIN rail conforming to EN 50022. The Modicon MCM modular safety controller system provide flexibility and scalability from 8 inputs, 2 dual/4 single channel outputs up to 128 inputs, 16 dual/32 single channel outputs, up to 32 or 48 diagnostic status outputs. Modicon MCM modular safety controller system are designed to monitor multiple safety functions on and around a machine to minimise the risk of people accessing the dangerous moving parts of the machine.
View AllClose