- color:
- Dark gray
- conformity marking:
- CE
- connection technology inputs outputs:
- 8 x CAGE CLAMP
- connection type 1:
- Inputs/outputs
- country of origin sales organisation germany:
- DE
- current carrying capacity power jumper contacts:
- 0.416666666666667
- depth:
- 67.8 mm / 2.669 inch
- depth from upper edge of din rail:
- 60.6 mm / 2.386 inch
- dielectric strength:
- 2.5 kV (AC)/3.5 kV (DC): per EN 60870-2-1
- emc emission of interference:
- Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
- emc immunity to interference:
- Per EN 61000-6-1, -2: EN 61131-2: marine applications: EN 50121-3-2: EN 50121-4, -5: EN 60255-26: EN 60870-2-1: EN 61850-3: IEC 61000-6-5: IEEE 1613: VDEW: 1994
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.25 2.5 mm / 24 14 AWG
- fire load:
- 0.147 MJ
- height:
- 100 mm / 3.937 inch
- housing material:
- Polycarbonate: polyamide 6.6
- indicators:
- LED (A, E) green: Status DI 1, DI 2
- input characteristic:
- High-side/low-side switching, configurable
- input current per channel for signal 1 typ:
- 2.5 mA
- input data width internal max:
- 2 bits
- input filter digital:
- 3 ms
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- number of digital inputs:
- 2
- number of incoming power jumper contacts:
- 2
- number of outgoing power jumper contacts:
- 2
- operating altitude:
- Without temperature derating: 0 2000 m: with temperature derating: 2000 5000 m (0.5 K/100 m): 5000 m (max.)
- overvoltage category:
- Nominal voltage 110 V: III (EN 61010-1 / up to 2.000 m): II (EN 61010-1 / up to 5.000 m)
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per EN 61010-1
- power consumption 5 v system supply:
- 2.5 mA
- protection type:
- IP20
- rated surge voltage:
- 5.0 kV (EN 60870-2-1 / Class VW3): 4.0 kV (UL 508): 4.0 kV (EN 61010-1 to 2000 m): 2.5 kV (EN 61010-1 to 5000 m)
- relative humidity with condensation:
- Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
- relative humidity without condensation:
- 0.95
- sensor connection:
- 2 x (2-wire)
- shock resistance:
- Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks: 25g/6 ms/1,000 shocks), EN 50155, EN 61373
- signal type:
- Voltage
- solid conductor:
- 0.25 2.5 mm / 24 14 AWG
- strip length:
- 8 9 mm / 0.31 0.35 inch
- supply voltage field:
- 110 VDC (-25 +30 %): via power jumper contacts (power supply via blade contact: transmission via spring contact)
- supply voltage sensor:
- 110 VDC
- supply voltage system:
- 5 VDC: via data contacts
- surrounding air temperature operation:
- -40 70 C
- surrounding air temperature storage:
- -40 85 C
- total number of channels module:
- 2
- vibration resistance:
- Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155: EN 61373
- voltage range for signal 0:
- 14 +50 VDC
- voltage range for signal 1:
- 70 143 VDC
- voltage signal type:
- 110 VDC
- weight:
- 48.000 g
- width: